1、卷首語(yǔ) Preface朋友,感謝你選用了本公司生產(chǎn)的冷凍式壓縮空氣十燥機(jī)。相 信它定能在您的生產(chǎn)線(xiàn)上,為解決壓縮空氣凈化問(wèn)題助一臂之力。Dear friends, thank you fbr choosing the Companys Refrigeration Compressed Air Drier. We believe that it surely will be helpful in solving the problem of compressed air purification on your lines.盡管該設(shè)備的功能控制,操作簡(jiǎn)單,設(shè)計(jì)新穎,出廠(chǎng)前均通過(guò) 了嚴(yán)格的品質(zhì)測(cè)試
2、。但為了您能準(zhǔn)確了解其安裝條件、運(yùn)行工況、 技術(shù)指標(biāo)和電器控制功能以及保養(yǎng)常識(shí),現(xiàn)將本說(shuō)明書(shū)介紹 給您,希望您在百忙之中閱讀。Although the equipment is simple in function, control and operation, novel in design and has undergone strict quality test at the factory, this Instruction Manual provides you a precise understanding of its installation conditions, opera
3、tion conditions, technical indexes and electrical control, hoping you to when you are free.本公司創(chuàng)建幾十年來(lái),我們?nèi)w同仁,吸取世界各國(guó)名廠(chǎng)之精 華,聘請(qǐng)谷輪、松下公司的高級(jí)工程師做顧問(wèn),與本公司工程技 術(shù)人員通力合作,改良創(chuàng)新,研究制造的太安伊僑系列產(chǎn)品已廣 泛用于化學(xué)、機(jī)械、輕紡、交通、電子、食品、制藥工業(yè)等各個(gè) 領(lǐng)域,深受用戶(hù)好評(píng)。以質(zhì)量取勝,以服務(wù)取信是我們的經(jīng)營(yíng)宗 旨!我們真誠(chéng)的希望您將設(shè)備運(yùn)行中的某些不足和良好建議反饋 我司。并祝安康!In more than decades since f
4、oundation of the Company, our colleagues absorb the essence of famous companies all over the world, recruit senior engineers from Copeland and Panasonic as advisors to fully cooperate with engineers and technicians of the Company in improvement and innovation, and the TAYQ series that are researched
5、 and manufactured have been widely applied in areas including chemical, machine, light textile, transportation, electronic, food and pharmacy and has won favorable comment from customers. To succeed with quality and to be trusted by service is our operation policy. We sincerely hope you are free to
6、feed back any weakness or helpful advices during equipment operation to our Company; we highly appreciate your business.目錄Table of Contents、安裝注意事項(xiàng)3-4Notices on Installation二、配置n. Configuration5-7三、操作指南HI. Operation Guidance四、保護(hù)功能IV. Protection7-8五、日檢與保養(yǎng)Daily Inspection and Maintenance六、VI.常見(jiàn)故障Common
7、 Failures七、電器電路圖VIL Electrical Circuit Diagramaulb lent temperature minder 35 Cabove bOcm一、安裝注意事項(xiàng):I . Notices on Installation1、安裝時(shí),應(yīng)盡量將機(jī)器放平。傾斜裝置會(huì)產(chǎn)生雜音、影響壽命和排 水。.During installation, the machine shall be placed as horizontally as possible, since an inclined unit may generate noise and influence the li
8、fetime and drainage.2、與空壓機(jī)、管路的連接應(yīng)采用軟管和減震墊,避免將空壓機(jī)的震動(dòng) 傳遞到干燥機(jī)。否則,會(huì)造成儀表和控制件失準(zhǔn)。.The air compressor and pipelines shall be connected with hose and shock reducing pad, to avoid transmission of air compressors vibration to the drier, or loss of precision may be caused against the meters and controls.3、陽(yáng)光直射會(huì)
9、影響冷凝器散熱,環(huán)境溫度不應(yīng)超過(guò)38 r。雨水淋漓、 潮濕的地方,會(huì)造成電氣短路、器件生銹。Direct exposure to sunshine may influence the cooling of condenser, with an ambient temperature not more than 38C. Rainfall and damp may cause short circuit and rust.4、嚴(yán)禁安裝在油煙、噴漆、 木屑、粉塵污染較重的場(chǎng)所。阻 塞腐蝕散熱器,是干燥機(jī)(氣冷 式)損壞的重要原因。W. It is not allowed to install wh
10、ere there is heavy pollution of oil fume, wood scraps and dust. A jammed and erosive cooler is the major factor of damages against the drier (air cooling)5、干燥機(jī)的四周應(yīng)留有不小于50cm散熱和保養(yǎng)空間。如安裝在 空壓機(jī)房要加裝換氣扇。V.A space not less than 50cm shall be reserved around the drier for cooling and maintenance. For example
11、, an exhaust fan shall be equipped in the air compressor room.6、多臺(tái)機(jī)器安裝在同一地 方時(shí),不要有散熱網(wǎng)相 對(duì)的情形。W . Opposition of cooling network shall be avoided when multiple units are installed at the same place.7、水冷式特別提醒:W. Special alerts for water cooling model:a、配備足夠的冷卻水塔。 用自來(lái)水作散熱、水壓不穩(wěn)、 浪費(fèi)大,機(jī)器工作不穩(wěn)定。With enough coo
12、ling tower. With tap water for cooling, the water pressure is unsteady, with great waste and unstable operation of machine.b。注意水源質(zhì)量。雜質(zhì)、 水垢多的會(huì)影響散熱效果。b. Pay attention to the water sources quality. Too much foreign substances and scale may influence the cooling effect.二、配置:II. Configuration:1、核準(zhǔn)待裝設(shè)備的處理
13、氣Nm3/min,應(yīng)和空壓機(jī)的排氣量Nm3/min匹 配。通常干燥機(jī)的處理氣量應(yīng)盡量大于空壓機(jī)的排氣量。I .Verify the processing gas Nm3/min of the equipment to be installed, which shall match the exhaust Nm3/min of the air compressor. Generally, the air volume processed by the drier shall be larger than the exhaust of the air compressor as much as p
14、ossible.2、請(qǐng)配置BY-PASS (旁通)管路,傍路連接干燥機(jī),應(yīng)用活接方式, 以便于維修保養(yǎng)。配置的重量,不要全落在干燥機(jī)上,應(yīng)用吊桿和支撐架。Please configure the BY-PASS pipeline, and the Bypass connects the drier in the manner of loose joint for the ease of maintenance and care. The configured weight shall not fully fall on the drier and be supported by hanging
15、 road and supports.3、進(jìn)出管路應(yīng)用新管連接,連接舊有管路時(shí),請(qǐng)清洗管內(nèi)污垢。The inlet and outlet pipes shall be connected with new pipes and the dirt inside the pipe shall be washed when connecting old pipes.4、干燥機(jī)空氣入口前須 裝置精密過(guò)濾器,以過(guò)濾空壓 機(jī)和連接管產(chǎn)生的油雜質(zhì)和鐵 銹。Precision filter must be equipped in front of the driers air inlet, to filter
16、the oily foreign substances and rust generated from the air compressor and connecting pipes.5、按銘牌標(biāo)示配置適宜電源、接地線(xiàn)、漏電斷路器。電壓不穩(wěn)的地 區(qū),要安裝穩(wěn)壓器。切勿與空壓機(jī)共用一個(gè)電源開(kāi)關(guān)。電源線(xiàn)的配置須 符合標(biāo)準(zhǔn),切忌過(guò)小。A proper power supply, earth wire and leakage breaker shall be equipped in accordance with the instruction on the nameplate. In areas w
17、ith unsteady power voltage, a regulator shall be installed. Never use the same power switch with air compressor. The configuration of power cable must meet the standard, which shall not be too small.BYPASS2旁路(旁通)配管:-57 tie舞慘時(shí)才能祈下rennovab I e jo i ntsare n嘩偵尊孟列丫 wh i chi cai bedur ing ma i mtentaniM有
18、了旁路我在綠葬維修 時(shí)系統(tǒng)仍能保持正常供氣With we客巖1 can st i I I rrs i nta in the nonma I a i r supp I dbr mg care and nd interaripe繭柬用活面接頭1、2 閥門(mén)(Valves) 3 旁路側(cè)閥門(mén)(Valve on the side of bypass)壓縮空氣出口(Compressed air outlet)壓縮空氣入口(Compressed air inlet)6活動(dòng)接頭(UNION,活接)Removable Joints (UNION, loose connection)三、操作指南:III.Opera
19、tion Guidance1、首次使用時(shí),請(qǐng)先確認(rèn)電源電壓、頻率是否正確,漏電開(kāi)關(guān),接地 線(xiàn)是否接妥!I .For first time of operation, please check if the power voltage and frequency are correct and if the leakage switch and earth wire are properly connected.2、合上電源,POWER (電源)指示燈亮;所設(shè)定的排水選擇鍵信號(hào)燈 (如:S1或S2)亮。Switch on the power supply and POWER (power sup
20、ply) LED will be on. The drainage selection button LED (e.g. S1 or S2) that have been set will be on.3、按或旋轉(zhuǎn)ON (啟動(dòng))鍵,RUN (運(yùn)行)燈亮,壓縮機(jī)、散熱馬達(dá) 開(kāi)始運(yùn)轉(zhuǎn),整機(jī)開(kāi)始工作。Push or turn ON (Start) button, RUN (run) LED will be on, the compressor and cooling motor start running and the whole machine starts operation.*當(dāng)關(guān)機(jī)后立即開(kāi)
21、機(jī)(或斷電后即刻復(fù)電)電腦將進(jìn)行高低壓兩側(cè)的 蒸發(fā)壓力校驗(yàn),此時(shí),原設(shè)定的排水選擇信號(hào)(S1或S2)閃爍,壓力平衡 后自動(dòng)進(jìn)入工況運(yùn)行RUN(運(yùn)行) 燈閃爍。壓力平衡自動(dòng)進(jìn)入工況 運(yùn)行(時(shí)長(zhǎng)約為1MIN)*When powering on immediately after powering off (or recovering immediately after deenergization), the PC will hold the vaporization pressure test on both sides of high and low pressure. At that tim
22、e, the originally set drainage selection signal (S1 or S2) will flash and the working condition will be automatically accessed after the pressure is balanced, with RUN (run) LED on. The operation will be started under working conditions after pressure is balanced (1 MIN of time length)4、EVAPORATOR P
23、RESS(低壓冷媒蒸發(fā)壓力表)此時(shí)壓力開(kāi)始下降,進(jìn)入設(shè)定工況后,使用R-12 冷媒之機(jī)型,指針應(yīng)在1.2-3.0Kg/cm2。r-22冷媒之機(jī)型,指針應(yīng)在 3.0-6.0Kg/cm2。EVAPORATORPRESS (Low pressure cool medium vaporization pressure meter), at that time, the pressure begins to drop. After accessing to the set working condition, the hand will point to 1.2-3.0Kg/cm2 for R-12 c
24、ool medium model and 3.0-6.0Kg/cm2 for R-22 cool medium model.5、75AS (WS)以上機(jī)型配置HIGH PRESS (高壓冷媒蒸發(fā)壓力表) 此時(shí)壓力開(kāi)始上升,正常范圍在12-20Kg/cm??肇?fù)荷時(shí)稍有偏低,滿(mǎn)負(fù)荷 或散熱不良時(shí),稍有偏高。The configuration of HIGH PRESS (High pressure cool medium vaporization pressure meter) for models above 75AS (WS). At that time, the pressure begin
25、s to increase, with a normal scope of 12-20Kg/cm. It will be lower for empty load and higher for full load or defective cooling.6、AIR OUT POWER (空氣出口壓力表)和 AIR IN POWER (空氣進(jìn) 口壓力表)分別顯示機(jī)組空氣出口、進(jìn)口的空氣壓力。AIR OUT POWER (Air outlet pressure meter) and AIR IN POWER (Air inlet pressure meterO respectively show
26、s the air pressure of air inlet and outlet of the machine assembly.7、DRAIN (排水選擇鍵)DRAIN指示燈表示排水時(shí)間,可根據(jù)用氣 量的大小、環(huán)境溫度自由設(shè)置(一般7.5AS-20ASCWS)選擇SI, 30AS(WS) -50AS (WS)選擇S2, 75AS (WS) -200AS (WS)選擇S3, 250AS (WS) 以上選擇S4);更改設(shè)置只需輕按排水鍵即可。停機(jī)時(shí)按排水鍵或運(yùn)行中 長(zhǎng)按排水鍵3S,可試驗(yàn)電子排水器和排水旋風(fēng)溝道是否暢通。VH.DRAIN (Drainage selection button)
27、. DRAIN LED shows the drainage time, which can be freely set in accordance with the air consumption and ambient temperature (generally, SI for 7.5AS-20AS (WS) , S2 for 30AS (WS) -50AS(WS) ,S3 for 75AS(WS) -200AS(WS) and S4 for above 250AS(WS). To modify the setting, just slightly push the drainage b
28、utton. To stop, push the drainage button or long press drainage button for 3S during operation. The electronic drainer or draining cyclone channel can be test for smoothness.8、MANUAL DRIVE ARAIN (手動(dòng)排水)空氣升到工況壓力后,多次 開(kāi)啟、關(guān)閉此閥可將管道中的各種殘余雜質(zhì)排出,每半月操作一次可延長(zhǎng) 自動(dòng)排水器的使用壽命。手動(dòng)排水器接口亦可用來(lái)清洗、吹凈散熱排、冷 凝器等處之灰塵。此接口變可根據(jù)需要另接浮
29、球式自動(dòng)排水器MANUAL DRIVE ARAIN (manual drainage). After the air pressure is increased to the working condition pressure, the residuals in the pipes can be drained by opening and closing this valve repeatedly. Monthly operation may extend the lifetime of the automatic drainer. The interface of the manual
30、drainer can be used for washing or blowing dust on the cooling row or condensers, which can additionally connect with the ball float automatic drainer in accordance with the demands.9、關(guān)機(jī)時(shí),輕按OFF (停止)鍵即可。然后斷開(kāi)電源和氣源。IX. To stop the machine, just slightly push OFF (Stop) button. Then disconnect the power
31、 supply and air supply.四、保護(hù)功能:IV. Protect i on:1、HIGH PROTECTION(高壓保護(hù)):當(dāng)環(huán)境溫度過(guò)高、散熱排被堵、 冷卻風(fēng)機(jī)不良時(shí),高壓保護(hù)指示燈亮并自動(dòng)切斷電源,整機(jī)停止運(yùn)轉(zhuǎn)。 RESET右鍵為高壓復(fù)位鍵,排除上述故障后,按下高壓復(fù)位鍵,方可重新 啟動(dòng)機(jī)器。I . HIGH PROTECTION (High pressure protection): when the ambient temperature is too high, the cooling row is jammed and the cooling blower is
32、defective, the HIGH PROTECTION LED will be on, the power will be disconnected automatically and the whole machine will stop running. The right button of RESET is the High Pressure Reset Button. After the above failures are removed, the machine can be restarted only by pushing the High Pressure Reset
33、 Button.2、LOW PROTECTION (低壓保護(hù));當(dāng)冷媒泄漏、機(jī)器冰堵、系統(tǒng)膨 脹閥(毛細(xì)管)和過(guò)濾器臟堵時(shí),低壓保護(hù)指示燈亮并自動(dòng)切斷電源,整 機(jī)停止運(yùn)轉(zhuǎn)。RESET左鍵為復(fù)位鍵,排除上述故障后,按下低壓復(fù)位鍵, 方可重新啟動(dòng)機(jī)器。II .LOW PROTECTION (Low pressure protection): when cool medium leaks, the machine jammed and the system expansion valve(capillary pipe) and filter are jammed by dirt, the LOW P
34、ROTECTION LED is on, the power will be disconnected automatically and the whole machine will stop running. The left button of RESET is the Reset Button. After the above failures are removed, the machine can be restarted only by pushing the Low Pressure Reset Button.3、OVERLOAD PROTECTION (過(guò)載保護(hù));當(dāng)供電電壓
35、低于或高于 額定電壓10%,機(jī)器處于超負(fù)荷狀態(tài)、壓縮機(jī)散熱馬達(dá)短路時(shí),過(guò)載保護(hù) 指示燈并自動(dòng)切斷電源,整機(jī)停止運(yùn)轉(zhuǎn),排除上述故障后,按下熱繼電器 復(fù)位手柄,方可重新啟動(dòng)機(jī)器。III. OVERLOAD PROTECTION (Overload protection): when the voltage of the power supply is 10% lower or higher than the voltage ratings, the machine is under the overload state and the cooling motor of compressor is
36、under short circuit, the OVERLOAD PROTECTION LED will be on, the power will be disconnected and the whole machine stops running. After the above failures are removed, the machine can be restarted only by pushing the Heat Relay Reset Handle.五、日檢與保養(yǎng):V. Daily Inspection and Maintenance1、每日開(kāi)機(jī)前,要確認(rèn)供電電源是否
37、正確。.Check if the power supply is OK prior to daily startup.2、使用環(huán)境溫度不應(yīng)高于38Co.The temperature of operating temperature shall not be more than 38C.3、將BY-PASS的傍路閥關(guān)閉,干燥機(jī)出入口閥打開(kāi)。III.Turn off the bypass valve of the BY-PASS and turn on the inlet and outlet valves of the drier.4、水冷式的冷卻水塔、抽水馬達(dá)、水源是否正常。IV .If t
38、he water cooling tower, pump motor and water are OK.5、每周需用壓縮空氣吹槍和干毛刷清潔冷凝器鰭片一至二次。V. The condensers extended surface shall be cleaned once or twice aweek with compressed air blowing gun and dry brushes.6、每月需用中性洗滌劑,清洗浮球式自動(dòng)排水器和水冷式散熱器一次。 采用電動(dòng)排水器的機(jī)器,需將電磁閥拆下,用壓縮空氣反復(fù)吹凈蒸發(fā)室、 旋分管內(nèi)的油垢和雜質(zhì)及電磁閥通道。VI.The ball float
39、 automatic drainer and water cooling radiator shall be cleaned once a month with neutral detergent. For machines with electric drainer, the electromagnetic valve shall be disassembled, and the oily dirt and foreign substances in the vaporization chamber and cyclone pipes as well as the electromagnet
40、ic valve channels be blown repeatedly by compressed air.7、例行檢查各接線(xiàn)處和端子有無(wú)松脫。VH. Regularly check if the connectors and terminals are loose.六、常見(jiàn)故障排除廠(chǎng)So Iut i ons of Common Failures()機(jī)器不能啟動(dòng)(I) Machine unabIe to start.現(xiàn)象Failures原因 Causes排除方法S olutions無(wú)電源No Power supply保險(xiǎn)絲溶斷或無(wú)熔絲開(kāi)閉 跳脫Blown fuse or non-fuseO
41、N/FF trip確認(rèn)電源是否有缺相短路檢查 保險(xiǎn)絲或無(wú)熔絲開(kāi)關(guān)Verify if there is phase loss or short circuit for the power supply and check the fuse or non-fuse switch.斷線(xiàn)Wire breakage找出斷線(xiàn)處,加以檢修Find the wire breakage and repair.有電源但 不能啟動(dòng)Unable to start with power.電壓異?;螂娫淳€(xiàn)太長(zhǎng)(電 壓降)Abnormal voltage or too long power cable (Voltage d
42、rop)請(qǐng)照銘牌上額定電壓指示Please follow the instruction on rated voltage on the nameplate.開(kāi)關(guān)不良Defective switch換新開(kāi)關(guān)Replace with a new switch接觸器不良Defective contactor接新接觸器Connect with a new contactor過(guò)載電驛(OVER RELAY) Over Relay (OVER RELAY)不良換新過(guò)載電驛Replace with the defective overload relay with a new one.電容器不良Defec
43、tive capacitor換新電容器Replace with a new capacitor啟動(dòng)電驛不良換新啟 動(dòng)電驛 Replace with aDefective start relaynew start relay高低壓壓力開(kāi)關(guān)不良Defective High/Low voltage pressure switch換新高低壓壓力開(kāi)關(guān) Replace with a new one.溫度開(kāi)關(guān)不良Defective temperature switch換新溫度開(kāi)關(guān) Replace with a new temperature switch壓縮機(jī)不良Defective compressor換新
44、壓縮機(jī)Replace with a new compressor高低壓跳脫后,未復(fù)歸 high/low voltage not reset after tripping找出跳 脫原因再RESET Find out the causes of tripping and then RESET電磁開(kāi)關(guān)OL未復(fù)歸 Electromagnetic switch OL not reset.找出跳脫原因后,再RESET Find out the causes of tripping and then RESET油壓開(kāi)關(guān)未復(fù)歸Oil pressure switch not reset找出原因后再 RESET
45、Find out the cause and then reset.溫度開(kāi)關(guān)設(shè)定誤差Error temperature switch setting重新設(shè)定或換新溫度開(kāi)關(guān)Reset or replace with a new temperature.壓縮機(jī)不良-Defective compressor換新壓縮機(jī) Replace with a new compressor(二)啟動(dòng)后運(yùn)轉(zhuǎn)不良(I I) Defective Operation after Startup現(xiàn)象Failures原因Causes排除方法Solutions電壓異常Abnormal voltage啟動(dòng)不久后,電線(xiàn)短路產(chǎn)生燒焦
46、味道。 Burning smell generated by short circuit shortly after startup連鎖控制線(xiàn)路及開(kāi)關(guān)新配 置New configuration of interlock control circuit as well as switches高壓跳脫雖然復(fù) 歸還是不能啟動(dòng) Unable to start up although the high voltage tripping reset.壓力開(kāi)關(guān)不良Defective pressure switch換新壓力開(kāi)關(guān)Replace with a new pressure switch風(fēng)扇不良Defe
47、ctive fan換新風(fēng)扇馬達(dá)Replace with a new fan motor過(guò)載跳脫Overload trip查清原因或檢查電驛Find out causes or check the relay冷凝器積垢Condenser begriming清洗Cleaning冷媒太多適當(dāng)減少冷媒Reduce coolToo much cool mediummedium properly環(huán)境溫度過(guò)高Toohighambienttemperature改善周?chē)鷾囟龋L(fēng)良好 位置 Improve the ambient temperature and with a positionwithgoodve
48、ntilation.膨脹閥阻塞域關(guān)閉Jammed or closed expansion valve換新彭脹閥Replace with a new expansion valve干燥過(guò)濾器阻塞Jammed drying filter換新干燥過(guò)濾器Replace with a new drying filter啟動(dòng)電驛不良Defective startup relay換新啟動(dòng)電驛 Replacewith a new startup relay過(guò)載電驛跳脫Overload relay trip電容器不良Defective capacitor換新電容器Replacewith a new capaci
49、tor壓力開(kāi)關(guān)不良Defective pressure switch換新壓力開(kāi)關(guān) Replacewith a new pressure switch壓縮機(jī)過(guò)負(fù)荷Overload of compressor干燥機(jī)過(guò)負(fù)荷,減少空氣處理量Drier overloaded, reduce volume of air processing干焊機(jī)要入口溫度過(guò)高Temperature too high at the inlet of dry welder增設(shè)前置冷卻器Front cooler added.周?chē)鷾囟冗^(guò)高Ambient temperature too high改善周?chē)鷾囟?,通風(fēng)良好位置Impro
50、ve theambient temperature and with a position with good ventilation.電驛設(shè)定電流值太低Current value of relay set too low調(diào)整電流值A(chǔ)djust current value電驛接觸不良Defective relay contact清理或換新Clean or replace with a new one電源欠相Insufficient phase of power supply查出電源欠相因素Find out the factor of insufficient phase.接觸器不良或接點(diǎn)不良D
51、efective contactor or contact清理或換新接觸器Clean or replace with a new contactor(三)正常運(yùn)轉(zhuǎn),但效果不佳(111) Norma I Operat i on with defect i ve effect現(xiàn)象 Failures原因Causes排除方法Solutions蒸發(fā)壓力(蒸 發(fā)溫度指示 過(guò)低) Evaporating pressure (indication ofevaporating pressure too low)蒸發(fā)溫度表(低壓表)不良Defectiveevaporatingthermometer (low pr
52、essure meter)換新蒸發(fā)溫度表(代壓表)Replace with a new evaporating thermometer (low pressure meter)熱氣旁路閥故障Hot gas bypass valve fails換新熱氣旁路閥Replace with a new hot gas bypass valve膨脹閥阻塞Jammed expansion valve換新膨脹閥Replace with anew expansion valve溫度開(kāi)關(guān)或壓力開(kāi)關(guān)設(shè)定 太低 Temperature switch or pressure switch set too low重新調(diào)整
53、設(shè)定Re-adjust settings.風(fēng)扇不停運(yùn)轉(zhuǎn)Uninterrupted running of fan查出原因或換新壓力開(kāi)關(guān)、溫 度開(kāi)關(guān) Find out the causes or replace with a new pressure switch or temperature switch冷媒雨Cool medium leakage查出漏何處,加灌冷媒Find out the leakage and add cool medium蒸發(fā)壓力(蒸 發(fā)溫度指示 過(guò)低) Evaporating pressure (indication of evaporating pressure to
54、o low)空氣入口溫度過(guò)高Temperature of air inlet too high增設(shè)前置冷卻器Front cooler added周?chē)鷾囟染諥mbient temperature too high改善周?chē)鷾囟龋L(fēng)良好位置Improvetheambienttemperature and with a position with good ventilation.熱氣旁路閥失效Hot gas bypass valve invalid調(diào)整或更新熱氣旁路閥Adjust or replace with hot gas bypass valve冷凝器阻塞Jammed condenser清洗
55、Cleaning空氣處理大 Large volume of air compressing重新設(shè)計(jì)匹配問(wèn)題Redesign the matching冷媒壓縮機(jī)進(jìn)排氣閥片磨 損Worn air inlet andoutlet valve plate of the cool medium compressor換新壓縮機(jī)Replace with a new compressor.(四)除水情形不良(IV) Poor water removal現(xiàn)象 Failures原因Causes排除方法Solutions空氣旁路閥沒(méi)有全開(kāi)Air bypass valve not fully open開(kāi)緊旁路閥Ful
56、ly open the bypass valve空氣沒(méi)有通過(guò)干燥機(jī)Air not passing the drier干燥機(jī)出入口閥門(mén)全開(kāi) Fully open the drier7 s inlet and outlet valve空氣流量大壓力降太大Air flow and pressure drop too large空壓源系統(tǒng)重新設(shè)計(jì)Re-design air compression sources system排水器前閥門(mén)未全開(kāi)或堵塞Front valve of drainer not fully open or jammed確認(rèn)閥門(mén)全開(kāi)位置或清除Locate the full open
57、 position of the valve or clear排水器不衣Drainer not work清新或換新Clean or replace with a new one排水管路高出自動(dòng)排水器Draining pipe higher than the automatic drainer排水管路重新裝置Re-install the draining pipes空壓機(jī)太大,干燥機(jī)太小,匹配 不 良 Air compressor too large, drier too small, defective matching重新設(shè)計(jì)匹配問(wèn)題Re-design the matching蒸發(fā)壓力(蒸
58、發(fā)溫度)批示 異常Evapor ating pressure(temp erature) indication abnormal蒸發(fā)溫度太高Evaporating temperature too high檢查空壓機(jī)氣源負(fù)荷Check the air sources load of the air compressor入口溫度太高Inlet temperature too high加裝冷卻器或儲(chǔ)氣罐Cooler or gas cylinder added.周?chē)h(huán)境空氣污蜀通風(fēng)不良Griming air or poor ventilation of ambient environment選擇適當(dāng)位
59、置或改善通風(fēng)Choose a proper position or improve the ventilation膨脹閥堵塞失效Expansion valves jammed or invalided.更新膨脹閥Replace with a new expansion valve冷媒漏Cool medium leakage查冷媒漏處,加灌冷媒Find out the cool medium leakage and add cool medium熱氣旁路閥失效Hot gas bypass valve invalid更新熱氣旁路閥Replace with a new hot gas bypass
60、valve儀表?yè)p壞Meters damaged更新儀表Replace with a new meter.(五)空氣壓降太大(V) Ai r pressure drop too much現(xiàn)象Failures原因Causes排除方法Solutions配管系統(tǒng)錯(cuò)誤Error pipefitting system管路閥門(mén)未全開(kāi)Pipe valves not fully open將閥門(mén)全開(kāi)Fully open the valves管徑太小Pipe diameter too small管徑加大Increase the pipe diameter管路太長(zhǎng),彎頭,接頭太多Pipeline too long,
溫馨提示
- 1. 本站所有資源如無(wú)特殊說(shuō)明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請(qǐng)下載最新的WinRAR軟件解壓。
- 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請(qǐng)聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶(hù)所有。
- 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁(yè)內(nèi)容里面會(huì)有圖紙預(yù)覽,若沒(méi)有圖紙預(yù)覽就沒(méi)有圖紙。
- 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
- 5. 人人文庫(kù)網(wǎng)僅提供信息存儲(chǔ)空間,僅對(duì)用戶(hù)上傳內(nèi)容的表現(xiàn)方式做保護(hù)處理,對(duì)用戶(hù)上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對(duì)任何下載內(nèi)容負(fù)責(zé)。
- 6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請(qǐng)與我們聯(lián)系,我們立即糾正。
- 7. 本站不保證下載資源的準(zhǔn)確性、安全性和完整性, 同時(shí)也不承擔(dān)用戶(hù)因使用這些下載資源對(duì)自己和他人造成任何形式的傷害或損失。
最新文檔
- 委托貨物運(yùn)輸服務(wù)合同范本
- 產(chǎn)品購(gòu)買(mǎi)合同范本
- 2024至2030年中國(guó)高壓空壓機(jī)行業(yè)投資前景及策略咨詢(xún)研究報(bào)告
- 勞務(wù)合同范本混凝土
- 2024至2030年液封式民用遠(yuǎn)傳水表項(xiàng)目投資價(jià)值分析報(bào)告
- 2024至2030年中國(guó)學(xué)習(xí)桌配套椅數(shù)據(jù)監(jiān)測(cè)研究報(bào)告
- 承包企業(yè)合同范本
- 話(huà)費(fèi)預(yù)繳合同范本
- 鋪面租用合同范本
- 浙江省東陽(yáng)市東陽(yáng)中學(xué)2025屆物理高三上期中教學(xué)質(zhì)量檢測(cè)試題含解析
- 建筑工程項(xiàng)目管理咨詢(xún)招標(biāo)(范本)
- 三位數(shù)除兩位數(shù)的除法練習(xí)題
- 慢性胃炎的中醫(yī)治療培訓(xùn)課件
- Python程序設(shè)計(jì)課件第7章面向?qū)ο蟪绦蛟O(shè)計(jì)
- 最新爆破安全規(guī)程
- 主題班會(huì)課防盜
- 幼兒園課件《撓撓小怪物》
- 教師教案檢查八大評(píng)分標(biāo)準(zhǔn)教案的評(píng)分標(biāo)準(zhǔn)
- 政府會(huì)計(jì)基礎(chǔ)知識(shí)講義
- 幼兒園整合式主題活動(dòng)設(shè)計(jì)案例《溫馨家園》
- 荒漠區(qū)生態(tài)治理(麥草沙障、植物固沙)施工方案
評(píng)論
0/150
提交評(píng)論