版權說明:本文檔由用戶提供并上傳,收益歸屬內容提供方,若內容存在侵權,請進行舉報或認領
文檔簡介
1、摘 要本工程地下1層,地上15層,其中1-3層為娛樂城, 每層有公共衛(wèi)生間若干,4層及以上為客房,建筑總高度59米。本論文就該建筑給水排水工程進行了設計,主要內容包括給水系統,消防系統,排水系統和雨水系統。其中給水系統中采用分區(qū)給水,低區(qū)采用市政管網直接供水,高區(qū)采用水池-水箱-水泵聯合供水。消防系統中包括有消火栓系統和自動噴水滅火系統,排水采用合流制排水,雨水采用重力內排水的方式,及時地將屋面雨水排出。此外還包括了給水引入管,排出的水至室外化糞池,及貯水池,水泵房,高位水箱等方面設計。本設計中給水干管和立管材均采用不銹鋼管,其他支管均采用鑄鐵管;消火栓給水管采用熱鍍鋅鋼管,自動噴水滅火系統管
2、道采用內外壁熱鍍鋅鋼管;排水管材采用鑄鐵管,水力計算按塑料管計。關鍵詞:高層酒店綜合樓;給水系統;消火栓系統;自動噴水滅火系統;排水系統;雨水系統ABSTRACT The construction of underground 1 floors, 15 floors on the ground, including 1-3 layers of entertainment city, each layer has a toilet several, more than 4 floors and rooms, building a total height of 59 meters.In this
3、 paper, the building water supply and drainage engineering for the design, the main content includes the water supply system, fire system, the drainage system and drainage system. Using the water where the water supply system, low zone by the municipal water supply pipe network directly, high using
4、the pool - tank joint water supply - water pump. Fire control system including fire hydrant system and automatic sprinkler system, the use of drainage drainage system, rain water by gravity drainage way, will promptly roof rainwater discharge. In addition to the water inlet pipe, the water discharge
5、d to the outdoor septic tank, and tank, pump house, water tank etc. Pipe and a vertical pipe are made of stainless steel pipe water dry in this design, the other branch pipe are made of cast iron pipe; fire hydrant water supply pipe using hot galvanized steel pipe, the inner and outer wall of galvan
6、ized steel pipe sprinkler system piping; drainage pipe using iron pipe, hydraulic calculation according to the plastic tube gauge.KEYWORDS: Upper Room Hotel building; water supply system; fire hydrant system; automatic sprinkler system; drainage system; drainage system.目 錄摘要1第一章 設計任務及資料 5第二章 建筑給水設計及
7、計算62.1 給水系統分區(qū)62.2給水系統的組成 72.3主要設計參數72.4給水管道布置與安裝 72.5室內給水系統計算 82.6生活水池及消防水池計算92.7設計秒流量計算 10 2.7.1II區(qū)給水立管計算152.8生活加壓設別的選擇19第三章 建筑排水系統的設計與計算 203.1排水方式的選擇203.2排水系統分區(qū) 203.3排水系統的組成 203.4排水管道及設備安裝要求 203.5住宅污水排水系統計算21 3.5.1客房污水橫管管道計算 21 3.5.2公共衛(wèi)生間計算 22 3.5.3客房污水立管管道計算 23第四章 建筑消防給水系統設計與計算254.1消火栓系數 25 4.1.1
8、設計參數 25 4.1.2消火栓系統的設計計算264.2消防水泵計算 274.3水泵接合器 284.4減壓穩(wěn)壓消火栓284.5消防排水 284.6消防水池計算 29第五章 雨水系統的設計及計算295.1塔樓雨水部分設計計算 295.2降雨強度 295.3裙樓雨水部分設計計算 31第六章 自動噴淋設計與計算 316.1噴頭流量 316.2流速316.3水力坡降316.4沿程水頭損失326.5局部損失326.6總損失 326.7終點壓力32論43參考文獻44第一章 設計任務及資料本工程地下1層,地上15層,其中1-3層為娛樂城, 每層有公共衛(wèi)生間若干,衛(wèi)生器具布置見平面圖。4層及以上為客房,建筑總
9、高度59米。該建筑給水水源為:生活用水,消防用水均以城市自來水為供水水源,市政水壓為0.3MPa,凍土深度0.3 m。繪制的圖紙數量不少于8張一號圖,要求為計算機繪圖。圖紙包括:首層平面圖;標準層平面圖;非標準層平面圖(當各層功能不同且有用水點時,均需繪一張);地下室平面圖;設備層平面圖(有無及數量可能不同,但與給排水有關即繪出);頂層平面圖;裙房平面圖(指有關的);衛(wèi)生大樣圖1:501:30;給水系統圖:1:100或無比例(以下同);排水系統圖1:100;消防系統圖1:100;雨水系統圖1:100;水泵房平面圖及系統圖,比例自定。圖紙要求:(1)平面圖:應繪出給水、排水、雨水、消防系統的水平
10、干管、支管、主管的位置。主管需注管號。消防平面需繪出消火栓、噴頭、閥門、水流指示器、減壓裝置、檢查閥門等,需注出管徑,噴水支管間距,噴頭間距等。設備層平面需繪清楚各類管線相互位置,連接關系,水箱、氣壓罐、水泵等設備位置、必要的閥門、儀表等。地下室平面,除各類管線外,還需按比例繪出吸水池(或貯水池)位置。生活泵、各類消防泵、污水池、污水泵、進戶管、水表節(jié)點,設備間連接管線,及閘門、儀表等。頂層平面圖,雨水斗的位置,通氣管出口,試驗消火栓等。(2)系統圖:給水、排水系統圖應繪出配水點符號、注出干管、主管、支管管徑、坡度、標高,檢查口、清掃口、通氣管及標高等。消防系統圖,除地面標高外、層數等外,需注
11、管徑、消火栓標高,水流指示器,閥門,儀表,火警信號閥等。2設計說明書、計算書要求:設計說明書:包括說明書的中文和英文摘要、關鍵詞;目錄和工程項目和設計要求概述,設計依據,設計參考資料,設計方案及方案比較情況等;設計計算書:各系統設計計算草圖及水力計算表,管道和設備的選型及布置,以及設計中尚存在的問題等。第二章 建筑給水設計及計算由于室外給水管網提供的壓力無法滿足建筑物的需要,市政給水部門又不允許直接從市政管網抽水,故在該建筑物地下室設貯水池,外網水首先進入貯水池,然后由變頻泵加壓供給建筑物的使用要求。2.1給水系統分區(qū)根據建筑給水排水設計規(guī)范(GB-50015 2003):高層建筑生活給水系統
12、豎向分區(qū),豎向分區(qū)的壓力應符合下列要求:各分區(qū)最低衛(wèi)生器具配水點處的靜水壓不宜小于0.45MPa。靜水壓大于0.35MPa的入戶管(或配水橫管),宜設減壓或調壓設施。各分區(qū)最不利配水點的水壓,應滿足用水水壓要求。居住建筑入戶管給水壓力不應大于0.35MPa。建筑高度不超過100米的建筑的生活給水系統,宜采用垂直分區(qū)并聯供水或分區(qū)減壓的供水方式;建筑超過100米的建筑,宜采用垂直串聯供水方式。已知市政常年可用水頭為0.3Mpa。根據最低衛(wèi)生器具配水點處靜水壓宜為0.45MPa的標準。以及充分利用原有水壓,將該建筑分為二個區(qū)。-13層為區(qū),由室外市政管網直接供水;415層為區(qū),由變頻水泵直接供水,
13、另附有隔膜氣壓罐。水泵的轉速隨著用水量的變化自動調節(jié),運轉靈活。變頻調速給水方式雖然高效節(jié)能、占地面積小,但其設備與管道復雜、維護管理不便、無法克服短時停電時供水的安全可靠性。該酒店的給水設計要求考慮短時停電的可能性,而且在其最高層設有水箱間,允許設置高位水箱。為保證供水安全可靠、簡化設備與管道,本設計確定中、高區(qū)選擇高位水箱-減壓閥供水方式。2.2、給水系統的組成 整個給水系統應包括引入管、水表井、給水管網和附件此外還包括高區(qū)所需的生活水池、加壓泵組。 2.3、主要設計參數 1、客房最高日生活用水定額按400L/人·d,用水小時數24h,時變化系數Kh=2.5。 2、停車庫地面沖洗
14、水最高日生活用水定額按2L/,用水小時數8h,時變化系數Kh=1。 2.4、給水管道布置與安裝 各層給水管采用暗裝敷設,室內支管和干管采用不銹鋼管;室外采用埋地,采用球墨鑄鐵給水管,法蘭連接;水泵房管道采用鋼襯塑復合管,法蘭連接。2.5室內給水系統計算 根據建筑設計資料、建筑性質和衛(wèi)生設備完善程度,確定相應的生活用水定額與小時變化系數。 按計算該建筑最高日用水量式中:最高日生活用水量();設計單位數(人或床或);單位用水定額L/(人天)或L/(床天)或L/(天)。按計算最大小時生活用水量式中:最大小時生活用水量();最高日生活用水量();每日使用時間(h);小時變化系數。用水量表用水名稱用水人
15、數用水單位用水量標準最高日水量水池存水 用水時間時變化系數 最大時水量 l/dt/dt/dhKd t/h 客房420床400168.0084.0024214.00工作人員40人2008.002.002420.67頂樓辦公室50人80.400.1041.20.123F包間320人6019.204.8041.25.76舞廳300人82.400.60121.20.242F包間200人6012.003.00121.21.201F餐廳150人609.002.25121.51.13裙樓員工100人10010.002.501221.67車庫用水420028.402.10811.05未預見水量以上各項之和的1
16、0% 23.74 2.58生產生活用水合計 261.14101.35 28.412.6、生活水池及消防水池計算由于資料不足,生活貯水容量按用戶最高日用水量的25%計算,局部客房和洗衣房按用戶最高日用水量的50%計算。經計算生活水池儲水量為101.35m³,取100m³。采用2個不銹鋼水箱串聯儲水,尺寸為5000×3000×4000(H)水池溢流排至集水坑,經排污管直接排入市政污水管。每個生活水箱進水管選DN100鋼塑管,管道流速取1.0m/s,進水流量為Q=1/4D2V=7.85 L/s=28.3 m3/h。水箱補水按3h算,28.3*2*3=169.8
17、 m³100 m³2.7、設計秒流量計算采用當量法計算。計算原理參照建筑給水排水設計規(guī)范GB50015-2003(2009年版),采用公共建筑采用當量法基本計算公式:qg=0.2aNg式中: qg計算管段的給水設計秒流量(L/s); Ng計算管段的衛(wèi)生器具給水當量總數; 根據建筑物用途而定的系數;取2.5。 建筑類型:宿舍(、類)、旅館、招待所、賓館計算結果:管段名稱管道流量L/s管長m累計當量管徑水力坡降mH2O/m流速m/s沿程損失mH2O1-20.153.20.75DN150.1801.160.573-40.241.111.20DN150.421.861.034-20
18、.341.001.70DN200.131.210.102-80.491.203.45DN200.2461.760.2968-70.153.20.75DN150.1801.160.575-60.241.111.20DN150.421.861.036-70.341.001.70DN200.131.210.107-80.491.203.45DN200.2461.760.2968-X0.982.004.90DN320.0571.1460.11管段名稱管道流量L/s管長m累計當量管徑水力坡降mH2O/m流速m/s沿程損失mH2O1-20.155.00.75DN150.17951.1660.8982-30
19、.393.51.95DN200.16171.4050.5343-50.541.702.70DN250.2951.9450.594-50.101.200.50DN150.0840.7770.0855-61.042.54.40DN250.23111.9780.58管段名稱管道流量L/s管長m累計當量管徑水力坡降mH2O/m流速m/s沿程損失mH2O1-21.21.00.50DN250.4102.6970.8202-31.61.01.00DN320.1421.8710.1423-41.701.01.50DN400.0801.490.0804-51.801.02.00DN400.0881.580.08
20、85-101.901.02.50DN400.0981.6750.0986-70.101.00.5DN150.0090.3380.0097-80.201.01.0DN200.0470.720.0478-90.301.01.5DN250.03160.6740.03169-100.401.02.0DN250.05370.8990.053710-112.200.204.50DN400.1241.9050.02411-122.241.105.25DN400.1241.9050.12412-132.306.00Dn400.1392.0280.41管段名稱管道流量L/s管長m累計當量標注管徑水力坡降mH2O
21、/m流速m/s沿程損失mH2O1-20.100.900.50DN150.0840.770.092-30.200.901.00DN200.0900.720.053-40.300.901.50DN200.1001.080.054-50.400.902.00DN250.0530.900.055-210.500.512.50DN250.0811.120.0810-110.100.900.50DN150.0840.770.0911-120.200.901.00DN200.0900.720.0512-140.300.901.50DN200.1001.080.059-101.301.096.50DN320.
22、0931.490.0310-111.350.807.25DN400.0521.190.0511-121.420.528.00DN400.0001.240.0613-140.150.740.75DN150.1801.160.186-70.100.900.50DN150.0840.770.097-80.200.901.00DN200.0900.720.058-90.300.901.50DN200.1001.080.059-150.400.902.00DN250.0530.900.0513-140.154.000.75DN150.0840.7770.335-201.704.0010.75DN400.
23、0801.4990.322.7.1、區(qū)給水立管水力計算管段名稱管道流量L/s管長m累計當量管徑水力坡降mH2O/m流速m/s沿程損失mH2O1-21.273.006.40DN320.0921.470.3322-31.793.0012.80DN400.0871.570.3163-42.193.0019.20DN500.0150.800.0544-52.533.0025.60DN500.0190.930.0715-62.833.0032.00DN500.0241.040.0876-73.103.0038.40DN650.0180.950.066同理可計算出I區(qū)給水立管相應數據:一區(qū)給水軸測圖:管段
24、名稱管道流量L/s管長m累計當量標注管徑水力坡降mH2O/m流速m/s沿程損失mH2O1-23.353.2644.80DN500.0211.020.2112-34.7337.0089.60DN650.04011.4440.2814-53.353.2644.80DN500.0211.020.2115-64.7337.0089.60DN650.04011.4440.2816-75.79712.00134.4DN650.05841.7690.7017-87.4812.00223.80DN800.05131.7820.6168-108.85212.00313.4DN1000.0161.150.1921
25、0-1110.03912.00403.1DN1000.02021.3040.24211-1210.58212.00447.9DN1000.02221.3750.26612-311.1012.00492.8DN1000.02431.4420.292二區(qū)給水管網二區(qū)給水水力計算表管段名稱管道流量L/s管長m累計當量標注管徑水力坡降mH2O/m流速m/s沿程損失mH2O1-23.353.2644.80DN500.0211.020.2112-34.7337.0089.60DN650.04011.4440.2814-53.353.2644.80DN500.0211.020.2115-64.7337.00
26、89.60DN650.04011.4440.2816-75.79712.00134.4DN650.05841.7690.7017-87.4812.00223.80DN800.05131.7820.6168-108.85212.00313.4DN1000.0161.150.19210-1110.03912.00403.1DN1000.02021.3040.24211-1210.58212.00447.9DN1000.02221.3750.26612-311.1012.00492.8DN1000.02431.4420.2923-x15.69712.00985.6DN1500.01090.9250.
27、1962.8、生活加壓設備的選擇-13層為區(qū),由室外市政管網直接供水;415層為II區(qū),由變頻水泵直接供水。Q泵=56.52立方米/小時15.70升/秒 備注 H泵=h1+h2+h3+h4 h1(幾何高差)=53.50米水頭h2(泵房損失)=3.00米水頭h3(管路損失)=10.34米水頭h4(配水點水頭)=15.00米水頭H泵=81.84米水頭管徑(mm)管路長度(m)水力坡降I管路損失(m)流速(m/s)DN150500.01130.570.94 局阻按 DN15053.500.01130.611.37DN65600.11306.782.22 局阻損失 2.39 沿程30%計 h3(管路損
28、失)=10.34米水頭高層衛(wèi)生間與地下室生活水箱高差H=5+46.50+2=53.5m ,水泵吸水管和壓水管的總水頭損失按H2=3.00m計算,局部水頭損失按沿程30%計,地下一層高區(qū)給水環(huán)網取DN150管徑,測量半環(huán)長度為50m。第三章 建筑排水系統設計與計算3.1、排水方式的選擇 根據環(huán)保的要求,結合室外排水系統的設置,該建筑采用分流制排水系統,洗滌廢水直接排入城市下水道,生活污水給室外化糞池處理后再排入城市下水道。 3.2、排水系統分區(qū) 1樓以上住宅的生活污水廢水在就近排入附近檢查井,底層住戶污、廢水單獨設置排水橫管,經匯合和單獨排放的方式排至最近檢查井。 由于建筑高度及每根污水水立管所
29、承擔的排水當量數較大,為使排水管道中氣壓波動盡量平穩(wěn),防止管道水封破壞,污水管道設伸頂通氣管。 3.3排水系統的組成本建筑排水系統的組成包括衛(wèi)生器具、排水管道、檢查口、清掃口、室外排水管道、檢查井、潛水泵、集水井、化糞池等。通氣系統包括伸頂通氣管和匯合通氣管。3.4排水管道及設備安裝要求 1、排水管材采用鑄鐵管。2、排水管與室外排水管連接處設置檢查井。 3、當排水管在中間層豎向拐彎時,排水支管與排水立管、排水橫管相連接時,排水支管與橫管連接點至立管底部水平距離L不得小于1.5m,排水豎支管與立管拐彎處的垂直距離h2不得小于0.6m。 4、當層高小于或等于4m時,污水立管和廢水立管應每層設一伸縮
30、節(jié)。 5、立管宜每6層設1個檢查口。在水流轉角小于135°的橫干管上應設檢查口式或清掃口。 6、立管管徑大于或等于110mm時在樓板貫穿部位應設置阻火圈或張度不小于500mm的防火套管。管徑大于或等于110mm的橫支管與暗設立管相連時,墻體貫穿部位應設置阻火圈或張度不小于300mm防火套管,且防火套管的明露部分張度不小宜小于200mm;防火套管、阻火圈等的耐火根不宜小于管道貫穿。3.5住宅污水排水系統的計算3.5.1客房污水橫管管道計算客房污水管道大樣圖客房污水計算表管段名稱管道流量L/s管道類型累計當量公稱直徑管材1-20.25立管0.7550鑄鐵2-51.23立管3.75100鑄
31、鐵3-40.25立管0.7550鑄鐵4-51.23立管3.75100鑄鐵3.5.2公共衛(wèi)生間計算公共衛(wèi)生間大樣圖公共衛(wèi)生間水力計算表管段名稱管道流量L/s管道類型累計當量公稱直徑管材1-20.25橫管0.7550鑄鐵2-30.25橫管0.75100鑄鐵3-40.47橫管1.50100鑄鐵4-50.52橫管2.25100鑄鐵5-60.56橫管3100鑄鐵7-82.0橫管7.5100鑄鐵8-92.12橫管12100鑄鐵9-102.23橫管16.5100鑄鐵10-222.32橫管21100鑄鐵11-120.25橫管0.75100鑄鐵12-130.34橫管1.05100鑄鐵13-140.44橫管1.3
32、5100鑄鐵14-150.48橫管1.65100鑄鐵17-181.5橫管4.5100鑄鐵18-192.04橫管9100鑄鐵19-212.16橫管13.5100鑄鐵16-200.25橫管0.7550鑄鐵20-210.25橫管0.7550鑄鐵21-222.17橫管14.25100鑄鐵22-X2.54橫管33.45100鑄鐵3.5.3客房污水立管管道計算根據建筑給水排水工程設計規(guī)范,本住宅樓排水設計秒流量可按以下公式計算: 式中: 計算管段排水設計秒流量,L/s; 計算管段衛(wèi)生器具排水當量總數; 計算管段上排水量最大的衛(wèi)生器具的排水流量,; 根據建筑物用途而定的系數,本設計為住宅樓,取2.5。客房污
33、水橫管值接納2個坐便器的排水量,排水當量為N=9q=0.12X2.5X3+1.5=2.4 L/S,橫管管徑取 DN100,坡度取通用坡度0.026??头繌U水管道設計計算圖:客房污水管道設計示意圖客房污水立管計算管段名稱管道流量L/s管道類型累計當量公稱直徑管材14-132.04立管9100鑄鐵13-122.26立管18100鑄鐵12-112.43立管27100鑄鐵11-102.58立管36100鑄鐵10-92.70立管45100鑄鐵9-82.82立管54100鑄鐵8-72.92立管63100鑄鐵7-63.02立管72100鑄鐵6-53.12立管81100鑄鐵5-43.20立管90100鑄鐵經計
34、算可得q=3.20L/S,小于規(guī)范表4.4.1專用DN100通氣立管,結合通氣管隔層連接排水量,4F層單層排水量客房的衛(wèi)生間排水量均小于規(guī)范4.4.15表排水橫管DN100的排水量。第四章 建筑消防給水系統設計與計算4.1、消火栓系統4.1.1、設計參數室內消火栓用水量10 l/s,充實水柱13m,每支水槍的流量5.2 l/s,每根豎管流量為10.4 l/s,消防立管管徑DN100。最低層消火栓所承受的靜水壓不大于1.0Mpa,可不分區(qū),采用一次供水的臨時高壓室內消火栓給水系統。4.1.2、消火栓系統的設計計算1)消火栓間距的確定 消火栓保護半徑:R=Ld+Ls 式中, R消火栓保護半徑(m)
35、Ld水龍帶敷設長度(m)乘以一個曲折系數0.8 則Ld=0.8*25=20m。Ls水槍充實水柱在水平面上的投影(m)Ls=12*cos45=8.49m。 消火栓的布置間距L=R2-b2式中, L消火栓的布置間距,m;b消火栓最大保護寬度(m)。 2)消防栓保護半徑按下列公式計算:Rf=Ld+Ls=20+8.49=28.49m ,消火栓最大保護寬度,bf=9.3m 消火栓布置間距:L=Rf2- bf2=22.65mHq=(f*Hm)/(1-*f* Hm)=(1.12*12)/(1-0.0097*1.12*12)=15.45kpa3)水槍噴嘴射流量按下式計算Qxh=BHq=(1.577*15.45
36、)=5.2L/s>5L/s。式中,Qxh水槍的射流量;L/s B水槍水流特性系數,與水槍噴嘴口徑有關, Hq水槍噴嘴處的壓力,kpa。故水槍噴射流量為5.2L/s。4)水龍帶采用襯膠水帶,Az=0.0172,水龍帶沿柱水頭損失按下式計算:Hd=Az*Ldq2xh故Hd=0.0172*20*5.22=9.3。5)消火栓出口壓力按下式計算:Hxh=Hq+hd故Hxh=19.98,取20m計算。6) 考慮2股水柱作用消火栓用水量Q=2×5.2=10.4L/s ,消火栓環(huán)狀給水管采用DN150鍍鋅鋼管,V=0.619m/s ,1000i=5.19。4.2、消防水泵計算最不利消火栓到消防
37、泵的高差為H=94.5+1.1=95.60m消火栓泵流量為40 L/S計算。消火栓揚程泵參數計算表Q泵=144立方米/小時40.00升/秒 備注 H泵=h1+h2+h3+h4 h1(幾何高差)=52.60米水頭h2(泵房損失)=3.00米水頭h3(管路損失)=10.32米水頭h4(出流水頭)=20.00米水頭H泵=85.92米水頭管徑(mm)管路長度(m)水力坡降I管路損失(m)流速(m/s)DN150500.06173.082.36DN150720.06174.442.36 沿程30%計 DN100350.01000.350.88DN7010.06040.061.42局部損失2.38h3(管
38、路損失)=10.32米水頭經計算可知消火栓揚程泵H=86m,Q=40l/s,選取XBD9/40-SLH。4.3水泵結合器 按高層民用建筑設計防火規(guī)范GB5004595規(guī)定每個水泵接合器的流量應按1015L/S計算本建筑室內消防設計水量為10.4L/S。故設置4個水泵結合器,型號為SQB100。4.4、減壓穩(wěn)壓消火栓消火栓栓口靜水壓力超過0.5MPa需要進行減壓措施。故地下室消火栓全采取減壓穩(wěn)壓式消火栓,型號為SNW65-H。4.5、消防排水 消防電梯下設置集水坑,消防廢水經廢水管排入集水井,經水泵提升排入市政污水管,水泵集水井處浮球開關自動控制停啟,也可手動停啟。4.6、消防水池計算根據規(guī)范消
39、火栓火宅延續(xù)時間為2小時,噴淋火宅延續(xù)時間為1小時:Q 室內=40*3.6*3=432m3Q噴淋=45*3.6*1=162m3Q合計=594m³經測量,地下室消防水池面積為226.6,取226計算。有效水深為H=600/226=2.66m,取2.7m。第五章 雨水系統的設計及計算該項目由4-15層客房塔樓和1-3層裙樓建筑構成,故屋塔、群樓面雨水系用內排水系統。雨水通過水斗、連接管、立管及埋地橫管等底層排出室外,接入市政雨水管道系統。雨水管道采用UPVC管,采用單斗系統排水。5.1、塔樓雨水部分設計計算雨水管道系統計算圖如下5.2、降雨強度城市:安徽- 合肥暴雨強度公式:q=3600
40、(1+0.76lgP)/(t+14)0.84。根據規(guī)范要求,設計重現期P=5年,降雨歷時t=5min,暴雨強度按江蘇鹽城計算,q= 464.71 L/s,測得塔樓屋頂回水面積為2329.75,取2330計算。雨水設計流量公式:Q=(*F*q5)/10000 (1)Q=(*F*h5)/3600 (2)式中,徑流系數,屋面取0.9; Q屋面雨水設計流量,L/s; F屋面設計匯水面積,m2; q5當地降雨歷時為5min的暴雨強度,L/(s·104·m2) h5當地降雨歷時為5min的小時降雨厚度,mm/h。規(guī)范中有關于雨水設計的流量公式為:Q=k·m·q
41、83;F式中,Q雨水設計流量,L/s; m流量徑流系數; q設計暴雨強度,(L/(s·hm2); F匯水面積,(hm2); k校正系數,一般取1。當屋面坡度較大時,且短時積水會造成危害時,取1.5。故Q=1*1*464.71*2330/1000=108.27L/s。屋面布置了7個87式雨水斗,每個雨水斗的流量為Q=108.27/7=7.02L/s。65、87、(79)雨水斗的最大泄流量口徑(mm)75100150200泄流量(L/s)812-1626-3640-56小于立管為DN100的87式雨水斗流量,符合實際需求。5.3、裙樓雨水部分設計計算經測量裙樓4F露天部分面積為4770.
42、1,側墻部分面積為103*36/2=1854,Q=1*1*6624.1*534.14/1000= 353.82L/s。第六章 自動噴淋設計與計算計算原理參照自動噴水滅火系統設計規(guī)范GB 50084-2001(2005年版) 基本計算公式: 6.1、噴頭流量: 式中:q 噴頭處節(jié)點流量,L/min ; P 噴頭處水壓(噴頭工作壓力)MPa; K 噴頭流量系數。6.2、流速V: 式中: Q管段流量L/s; Dj管道的計算內徑(m)。6.3、水力坡降: 式中:i每米管道的水頭損失(mH20/m); V管道內水的平均流速(m/s); dj管道的計算內徑(m),取值應按管道的內徑減mm確定。6.4、沿程水頭損失: 式中:L - 管段長度m。6.5、局部損失(采用當量長度法): (當量) 式中:L(當量) - 管段當量長度,單位m(自動噴水滅火系統設計規(guī)范附錄C)。6.6、總損失: 6.7、終點壓力: 管段名稱起點壓力mH2O管道流量L/s管長m當量長度管徑mmK水力坡降mH2O/m流速m/s損失mH2O終點壓力mH2
溫馨提示
- 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請下載最新的WinRAR軟件解壓。
- 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請聯系上傳者。文件的所有權益歸上傳用戶所有。
- 3. 本站RAR壓縮包中若帶圖紙,網頁內容里面會有圖紙預覽,若沒有圖紙預覽就沒有圖紙。
- 4. 未經權益所有人同意不得將文件中的內容挪作商業(yè)或盈利用途。
- 5. 人人文庫網僅提供信息存儲空間,僅對用戶上傳內容的表現方式做保護處理,對用戶上傳分享的文檔內容本身不做任何修改或編輯,并不能對任何下載內容負責。
- 6. 下載文件中如有侵權或不適當內容,請與我們聯系,我們立即糾正。
- 7. 本站不保證下載資源的準確性、安全性和完整性, 同時也不承擔用戶因使用這些下載資源對自己和他人造成任何形式的傷害或損失。
最新文檔
- 云南省玉溪市民中2025年高三適應性調研考試化學試題含解析
- 弘揚民族精神增強愛國教育
- 山東省鄒城一中2025屆高考化學押題試卷含解析
- 2025屆浙江省杭州市七縣區(qū)高三第三次模擬考試化學試卷含解析
- 內蒙古一機集團第一中學2025年高三第二次調研化學試卷含解析
- 心梗病人的護理
- 福建省泉州市20023年第29屆WMO競賽三年級數學下學期競賽試卷
- 2024-2025學年河北省邢臺市四縣兄弟學校聯考高一上學期1月期末數學試卷(含答案)
- 上海市七寶高中2025屆高考化學考前最后一卷預測卷含解析
- 云南省曲靖市宣威民族中學2025屆高三最后一?;瘜W試題含解析
- 國家重點保護野生植物采集申請表
- 高中語文:陳情表
- 數字信息技術與中學思政課教育教學深度融合
- 江蘇省交通技師學院教師招聘考試真題2022
- 數據挖掘(第2版)PPT全套完整教學課件
- 2023年北京海淀高三一?;瘜W試題及參考答案
- 教師資格定期注冊申請表(樣表)
- 中國近現代史綱要(上海建橋學院)智慧樹知到答案章節(jié)測試2023年
- 外研版高中英語新教材必修三Unit1隨身課本-Understandingideas01
- 運動技能學習與控制課件第一章運動技能學習與控制概述
- GB/T 9575-2013橡膠和塑料軟管軟管規(guī)格和最大最小內徑及切割長度公差
評論
0/150
提交評論