NATIONALSTANDARD

'

OFTHEPEOPLESREPUBLICOFCHINA

CODEFORFIREPROTECTIONDESIGNOFBUILDINGS

(2018Edition)

GB50016-2014

'

-

'

,

Beijing2021ChineseeditionfirstpublishedinthePeoplesRepublicofChinain2018

EnlisheditionfirstublishedinthePeolesReublicofChinain2021

gppp

bChinaPlanninPress

yg

rd

,,

3FloorCTowerGuohonBuildin

gg

,,

No.A11Muxidi-BeiliXichenDistrict

g

Beiin100038

jg

PrintedinChinabyBeijingJingyintangGraphicPrintingCenter

?2018bytheMinistryofHousingandUrban-RuralDevelopmentof

thePeoplesRepublicofChina

Allrihtsreserved.Noartofthisublicationmabereroducedortransmittedinanformor

gppypy

,,,,,,

banmeansrahicelectronicormechanicalincludinhotocoinrecordin

yygpgppygg

,

oraninformationstoraeandretrievalsstemswithoutwrittenermissionoftheublisher.

ygypp

,,,

Thisbookissoldsubecttotheconditionthatitshallnotbwaoftradeorotherwisebelent

jyy

resoldhiredoutorotherwisecirculatedwithouttheublishersriorconsentinanformof

ppy

blindingorcoverotherthanthatinwhichthisispublishedandwithoutasimilarcondition

includingthisconditionbeingimposedonthesubsequentpurchaser.

ISBN978-7-5182-1364-1中華人民共和國住房和城鄉(xiāng)建設(shè)部公告

2021年第164號

住房和城鄉(xiāng)建設(shè)部關(guān)于發(fā)布《石油化工

鋼制設(shè)備抗震設(shè)計標準》等4項

工程建設(shè)標準英文版的公告

現(xiàn)批準《石油化工鋼制設(shè)備抗震設(shè)計標準》(CB/T50761-2018)、《石油化工鋼制設(shè)備抗

震鑒定標準》(GB/T51273-2018)、《石油化工工程數(shù)字化交付標準》(GB/T51296-2018)、

《建筑設(shè)計防火規(guī)范(2018年版)》(GB50016-2014)等4項工程建設(shè)標準英文版。工程建設(shè)

標準英文版與中文版出現(xiàn)異議時,以中文版為準。

該4項工程建設(shè)標準英文版由住房和城鄉(xiāng)建設(shè)部組織中國計劃出版社有限公司出版

發(fā)行。

中華人民共和國住房和城鄉(xiāng)建設(shè)部

2021年9月18日

AnnouncementoftheMinistryofHousingandUrban-Rural

'

DevelopmentofthePeoplesRepublicofChina

()

-

CodeforFireProtectionDesignofBuildings

-CodeforFireProtectionDesignof

Buildings,

,(,,,),,,,,,,,,

(,,),,,,,,(,,)

-()

StandardizationofEngineeringConstruction.

'

-

,

Explanationofthepartialrevisionofthecode

"

'

"-()

,

-

,

,

,,,

,,,,,,,,,,,,,

,,,,,,,,,,

()

,,,

,:

ChiefDevelopmentOrganization:

ParticipatingDevelopmentOrganizations:

ChiefDrafters:

·1·ChiefReviewers:

ZHOUChangWANGDongLIShucongJIANGGangZHUXianze

CHEXueyaDIWeiLIUWenliXUHongqingZHUANGSunyi

ZHAOLiangling

Translators:

NIZhaopengQIUPeifangWANGZongcunPENGLei

Reviewers:

LIUJiyangHURuiLIANDanjunLOUGuobiaoZHUGuoqing

LUWeidongZHANGHaiyanYANGXuebingWANGZhao

·2·AnnouncementoftheMinistryofHousingandUrban-Rural

'

DevelopmentofthePeoplesRepublicofChina

-

CodeforFireProtectionDesignofBuildings

CodeforFireProtectionDesignofBuildings

-,

,,,,,,,,,,(),,

,,,,,,,,,,,,,,,

,,,,,,,,(,,,),,,,,,

,,,,,,,,,,,,(,,,),,

,(,,,),(,),,,(,,,,),(,),(,,,

,),,,,,(),,,(,,,),,,,

,,,,,,,,,,,,,(,,),

,(,,,,),,(,,,,),,,,,,,,

,,,,(,,),,(,,),,,,,(,,),

,,,,(,,),,,,,,,,,,,

,,,,,,,,,,,,,,,,

,,,,,,,(,),,,,,

,,,(,,),,,,,,

-CodeofDesignonBuilding

FireProtectionandPrevention-CodeforFireProtectionDesignofTallBuilding

'

-,

'

-

,F(xiàn)oreword

-"

)"-"

CodeofDesignonBuildingFireProtectionandPreventionCodeforFireProtectionDesign

ofTallBuilding"-,

-CodeofDesignonBuildingFireProtectionandPrevention

-CodeforFireProtectionDesignofTallBuilding

,

,"

-",,

,

,

,,

,,,,

,,

-

,-

,,-

,,,,

,,

;,,

,,

;,

,,();

;

,,

;,

,-

-CodeofDesignon

BuildingFireProtectionandPrevention-()CodeforFireProtection

DesignofTallBuilding

·1·CodeofDesignonBuildingFireProtectionandPreventionCodeforFireProtection

DesignofTallBuilding,

(""""),

-

-

;,

--

,

,,

(,,

'

-

;

'

,

,

,

,,,

'

(,,

,,)

,,

ChiefDevelopmentOrganizations:

ParticipatingDevelopmentOrganizations:

·2·,

,

,

,

ChiefDrafters:

ChiefReviewers:

·3·Contents

………………()

……………()

…………………………()

………………………()

…………………()

………………………()

-………………()

,…………………()

…………()

………………()

………………()

……………………()

…………()

………………()

……………()

……()

-…()

……………………()

………………()

…………………()

-………………()

…………………()

……………()

………………()

……………()

…………()

………………………()

…………………()

……………()

………………………()

……………()

…………………()

…………………()

………………()

…………()

……………()

……………………()

…………()

-…………()

·1·……………()

………………………()

………………()

………………()

…………()

………()

……………()

………………………()

……………………()

………………()

………………()

………………()

……………………()

………………()

……………()

…………()

…………………()

……………()

……………()

……………()

……()

……()

--

-…………()

………………()

……………()

·2·1Generalprovisions

1.0.1Thiscodeisformulatedwithaviewtopreventingfireaccidentsinbuildings,reducingfire

hazardsandprotectingsafetyoflifeandproperty.

1.0.2Thiscodeisapplicabletothefollowingnewlyconstructed,enlargedandalteredbuildings:

1Factorybuildings;

2Storages;

3Civilbuildings;

4ClassA,B,Cliquidtanks(tankfarms);

5Combustibleandcombustion-supportinggastanks(tankfarms);

6Stackyardsforcombustibles;

7Urbanroadtunnels.

Ifdedicatednationalstandardsareavailable,thefireprotectiondesignofbuildingsforcivilair

defenseengineering,petroleumandnaturalgasengineering,petrochemicalengineering,fossilfuel

powerplantsandsubstationsshouldcomplywiththerequirementsofthosestandards.

1.0.3Thiscodeisnotapplicabletothefireprotectiondesignofbuildingssuchasfactorybuildings

(storages)forgunpowder,explosivesandtheirproductsaswellasfireworksandfirecrackers.

1.0.4Whereabuildingismulti-used,fireseparationsshallbeprovidedbetweendifferentuses.Fire

protectiondesignofbuildingsandtheareasofdifferentusesshallbedeterminedaccordingtothe

relevantrequirementsofthiscode.

1.0.5Fireprotectiondesignofbuildingsshallcomplywiththerelevantnationalmajorpolicies,and

guarantee,onthewhole,theoverallplanning,safetyandapplicability,advancedtechnologyaswellas

economicalrationalityaccordingtotheoccupanciesandfirehazardsofthebuilding.

1.0.6Inadditiontocomplywiththerequirementsofthiscode,buildingswithheightgreaterthan250m

shallbeprotectedwithstricterfireprotectionmeasuresaccordingtotheactualsituation.Fireprotection

designsolutionsofsuchbuildingsshallbediscussedandreviewedbythenationalfireauthorities.

1.0.7Inadditiontotherequirementsofthiscode,fireprotectiondesignofbuildingsshallalsocomply

withthosespecifiedintherelevantcurrentnationalstandards.

·1·2Termsandsymbols

2.1Terms

2.1.1high-risebuilding

Residentialbuildingswithbuildingheightgreaterthan27mandnon-single-storeyfactory

buildings,storagesandothercivilbuildingswithbuildingheightgreaterthan24m.

Note:ThecalculationofbuildingheightshallcomplywiththosespecifiedinAppendixAofthiscode.

2.1.2podium

Theancillarypartofahigh-risebuilding,whoseheightisnotgreaterthan24m,andisconnectedto

themainbodyofthehigh-risebuildingbutisbeyondtheprojectionrangeofthemainbody.

2.1.3importantpublicbuilding

Thecivilbuildingotherthanresidentialbuildingthatmaycauseheavycasualtiesandproperty

losses,severesocialimpactincaseoffire.

2.1.4smallcommercialspaces

Commercialspacessuchasshops,postoffices,banks,barbershopslocatedonthefirstfloororthe

firstandsecondfloorsoftheresidentialbuildings,withthebuildingareaofeachseparatedunitnot

2

greaterthan300m.

2.1.5highrackstorage

Rackstoragewithrackheightgreaterthan7mandwithmechanicaloperationorautomaticcontrol.

2.1.6semi-basement

Aspacehavingitsaverageclearheightgreaterthan1/3butlessthan1/2belowfinishedgroundlevel.

2.1.7basement

Aspacehavingmorethanhalfitsaverageclearheightbelowfinishedgroundlevel.

2.1.8openflamelocation

Anindoororoutdoorlocationwithopenflameorred-hotsubjects,excludingcookingutensils,

inductioncookerandthelikeinacivilbuilding.

2.1.9sparkingsite

Alocationlikechimneywithflyingfire,orforsuchoperationsasoutdoorgrindingwheel,electric

welding,gasweldingandgascutting.

2.1.10fire-resistancerating

Aperiodoftimethatstartsfromabuildingelement,componentorassemblythatareexposedto

fireunderstandardfireconditions,tothetimethattheylosebearingcapacity,integrityorinsulation,

expressedinhours.

2.1.11firepartitionwall

Noncombustiblewallinabuildingwhichpreventsfirefromspreadingtoadjoiningareaswithfire-

resistanceratingnotlessthanthespecifiedrequirementsofthecode.

2.1.12firewall

Noncombustiblewallwhichpreventsfirefromspreadingtoadjoiningbuildingsoradjoining

horizontalfirecompartmentswithfire-resistanceratingnotlessthan3.00h.

·2·2.1.13refugefloo(rroom)

Afloo(rroom)inabuildingthattemporarilyprotectspeoplefromfireandsmoke.

2.1.14exit

Entrancetoastaircase/externalstairsforevacuationofpeopleorthatdirectlyleadingtointernal

and/orexternalsafeplaces,includingstoreyexitandfinalexit.

2.1.15enclosedstairway

Staircasewithadooratitsentrancetopreventsmokeandheatfromenteringintoit.

2.1.16smokeproofstaircase

Staircasewithsuchfacilitiesassmokeproofvestibule,openbalconyorconcavecorrido(rcollectively

namedas"vestibule")atitsentrance,allthedoorsleadingtothevestibuleandstaircasearefiredoors,

whichpreventsmokeandheatfromenteringintoit.

2.1.17refugepassageway

Passagewayforpeopletorefugetemporarilyandevacuatesafelytotheoutsidebyproviding

smokeproofmeasuresandfirepartitionwallswithfire-resistanceratingnotlessthan3.00honboth

sides.

2.1.18flashpoint

Underspecifiedtestconditions,theminimumtemperature(determinedbyclosedcupmethod)ofa

liquidorsolidatwhichvaporgivesoffnearthesurfaceoftheliquidorsolidtoformanignitablemixture

withair,andwillflashinthepresenceofanignitionsource.

2.1.19lowerexplosivelimi(tLEL)

Theminimumconcentrationofthemixtureofcombustiblevapor,gasordustwithairthatis

capableofexplodinginthepresenceofanignitionsource.

2.1.20boil-overoil

Oilproductsthatcontainwaterandcanproducethermalwaveduringcombustion.

2.1.21fireseparationdistance

Aspatialseparationthatpreventsaburningbuildingfromignitingitsadjacentbuildingswithin

certaintimeandfacilitatesfire-fighting.

Note:ThecalculationmethodoffireseparationdistanceshallcomplywiththosespecifiedinAppendixBofthecode.

2.1.22firecompartment

Enclosedspacewithinabuildingseparatedfromadjoiningspacesbyfirewalls,floorsandother

constructionshavingaspecifiedfireresistance.

2.1.23solidstream

Ajetlengthfromthehosenozzletotheholewithdiameteras380mm,fromwhich90%ofthe

waterstreampassesthrough.

2.2Symbols

A—Pressurereliefarea;

C—Pressurereliefratio;

D—Diameterofstoragetank;

DN—Nominaldiameterofpipe;

ΔH—Heightdifferenceofbuildings;

·3·L—LengthofEnclosedsectionofatunnel;

N—Numberofpeople;

n—Numberofseats;

K—Characteristicindexofexplosion;

V—Volumeofbuildingandstackyardorthevolumeorcapacityoftankorcylinder;

W—Capacityofstackyardforcombustiblesorgrainsilo,binandbarn.

·4·3Factorybuildingsandstorages

3.1Classificationoffirehazards

3.1.1Firehazardofproductionshallbeclassifiedaccordingtosuchfactorsasthepropertiesand

quantityofsubstancesusedorgeneratedduringproduction.ItisclassifiedintoClassA,B,C,DandE,

andshallbeinaccordancewiththosespecifiedinTable3.1.1.

Table3.1.1Classificationoffirehazardsofproduction

Firehazardclass

Firehazardcharacteristicsofproductionusingorgeneratingthefollowingsubstances

ofproduction

1.Liquidwithflashpointlessthan28℃;

2.GaswithLELlessthan10%;

3.Substancesbeingcapableofspontaneousdecompositionatnormaltemperatureoroxidizingintheairandresultin

rapidspontaneousignitionorexplosion;

4.Substancesbeingcapableofgeneratingcombustiblegasandcausingcombustionorexplosionatnormal

temperatureundertheactionofwaterorthewatervaporintheair;

A

5.Strongoxidizerwhichtendstocausecombustionorexplosionincaseofmeetingacid,heat,impact,friction,

catalysisaswellasorganicsubstanceorflammableinorganicsubstanceslikesulphuretc.;

6.Substanceswhichcancausecombustionorexplosionincaseofbeingimpacted,rubbedorbeingexposedtooxidizer

andorganicsubstances;

7.Productionwheretheoperatingtemperatureinsidetheenclosedequipmentisnotlessthanthespontaneousignition

temperatureofthesubstance

1.Liquidwithflashpointnotlessthan28℃butlessthan60℃;

2.GaswithLELnotlessthan10%;

3.OxidizernotbelongingtoClassA;

B

4.FlammablesolidnotbelongingtoClassA;

5.Combustion-supportinggas;

6.Floatingdust,fiberandliquidfogdropwithflashpointnotlessthan60℃,whichiscapableofformingexplosive

mixturewiththeair

1.Liquidwithflashpointnotlessthan60℃;

C

2.Combustiblesolid

1.Productionwherenoncombustiblesubstanceisprocessed,withstrongradiantheat,sparkorflamefrequently

generatedathightemperatureormoltenstate;

D

2.Variousproductionwheregas,liquidandsolidareusedasfuelorgasandliquidcombustsforotherpurpose;

3.Difficultcombustiblesthatareusedorprocessedatambienttemperature

ENoncombustiblesthatareusedorprocessedatambienttemperature

·5·3.1.2Whenproductionwithdifferentfirehazardsiscarriedoutinthesamefactorybuildingorinany

firecompartmentthereof,thefirehazardclassificationofproductioninthatfactorybuildingorinthatfire

compartmentshallbedeterminedaccordingtothepartwithhigherfirehazard;whenthequantityof

flammablesorcombustiblesusedorgeneratedduringproductionissmallandisinsufficienttocause

explosion/firehazard,thefirehazardclassificationmaybedeterminedaccordingtotheactual

conditions;whenoneofthefollowingconditionsismet,thefirehazardclassificationmaybedetermined

accordingtothepartwithlowerfirehazard:

1Thefloorareaoftheproductionpartwithhigherfirehazardislessthan5%ofthegrossfloor

areaofthefloororthefirecompartmentortheareaofpaintspraysectioninClassDandEfactory

buildingsislessthan10%,andfirecannotspreadtootherpartsduringfireaccidentortheproduction

partwithhigherfirehazardhasbeentakenwitheffectivefirepreventionmeasures;

2TheareaofpaintspraysectioninClassDandEfactorybuildingsisnotlargerthan20%ofthe

grossfloorareaofthefirecompartment,providedthatthesectionisenclosedandnegativelypressurized,

combustiblegasdetectionandalarmsystemorautomaticexplosionsuppressionsystemisinstalled.

3.1.3Thefirehazardofstoredmaterialsshallbeclassifiedaccordingtosuchfactorsastheproperties

ofstoredmaterialsandthequantityofcombustiblesinthestoredmaterials.ItisclassifiedintoClassA,

B,C,DandE,andshallbeinaccordancewiththosespecifiedinTable3.1.3.

Table3.1.3Classificationoffirehazardsofstoredmaterials

Firehazardclassof

Firehazardcharacteristicsofstoredmaterials

storedmaterials

1.Liquidwithflashpointlessthan28℃;

2.GaswithLELlessthan10%,solidsubstancewhichcangenerategaswithLELlessthan10%undertheaction

ofwaterorthewatervaporintheair;

3.Substancesbeingcapableofspontaneousdecompositionatnormaltemperatureoroxidizingintheairandresult

inrapidspontaneousignitionorexplosion;

A4.Substancesbeingcapableofgeneratingcombustiblegasandcausingcombustionorexplosionatnormal

temperatureundertheactionofwaterorthewatervaporintheair;

5.Strongoxidizerwhichisapttocausecombustionorexplosionincaseofmeetingacid,heat,impactandfrictionas

wellasorganicsubstanceorflammableinorganicsubstanceslikesulphuretc.;

6.Substancewhichcancausecombustionorexplosionincaseofbeingimpacted,rubbedorbeingexposedto

oxidizerandorganicsubstance

1.Liquidwithflashpointnotlessthan28℃butlessthan60℃;

2.GaswithLELnotlessthan10%;

3.OxidizernotbelongingtoClassA;

4.FlammablesolidnotbelongingtoClassA;

B

5.Combustion-supportinggas;

6.Materialswhichoxidizeslowlyatnormaltemperatureifbeingexposedtotheairandcausespontaneousignition

duetoaccumulatedheat

1.Liquidwithflashpointnotlessthan60℃;

C

2.Combustiblesolid

D

Difficult-combustibles

ENoncombustibles

·6·3.1.4Whenmaterialswithdifferentfirehazardsarestoredinthesamestorageorinthesamefire

compartmentthereof,thefirehazardofthestorageorthefirecompartmentshallbedetermined

accordingtothestoredmaterialswiththehighestfirehazard.

3.1.5AsforthestoragesofClassDandE,iftheweightofcombustiblepackageislargerthan1/4of

thatofthestoredmaterialsorthevolumeofcombustiblepackageislargerthan1/2ofthatofthestored

materials,theclassificationofthefirehazardshallbeClassC.

3.2Fire-resistanceclassoffactorybuildingsandstorages

3.2.1Thefire-resistanceclassoffactorybuildingsandstoragesareclassifiedintoClassⅠ,Ⅱ,Ⅲand

Ⅳ.Thecombustibilityandfire-resistanceratingofcorrespondingbuildingelementsshallbenotless

thanthosespecifiedinTable3.2.1unlessotherwiserequiredbyprovisionsofthiscode.

Table3.2.1Combustibilityandfire-resistancerating(h)ofbuildingelementsfor

factorybuildingandstoragewithdifferentfire-resistanceclass

Fire-resistanceclass

Elements

ClassⅠClassⅡClassⅢClassⅣ

NoncombustibleNoncombustibleNoncombustibleNoncombustible

Firewall

3.003.003.003.00

NoncombustibleNoncombustibleNoncombustible

Difficult-combustible

Load-bearingwall

3.002.502.00

0.50

WallsofstaircaseandvestibuleNoncombustibleNoncombustibleNoncombustible

Difficult-combustible

Wall

Wallsofelevatorshaft2.002.001.50

0.50

PartitionwallsonbothsidesofNoncombustibleNoncombustibleNoncombustible

Difficult-combustible

exitpassageway1.001.000.50

0.25

NonbearingexteriorwallNoncombustibleNoncombustible

Difficult-combustibleDifficult-combustible

Roompartitionwall0.750.50

0.500.25

NoncombustibleNoncombustibleNoncombustible

Difficult-combustible

Column

3.002.502.00

0.50

NoncombustibleNoncombustibleNoncombustible

Difficult-combustible

Beam

2.001.501.00

0.50

NoncombustibleNoncombustibleNoncombustible

Difficult-combustible

Floor

1.501.000.75

0.50

NoncombustibleNoncombustible

Difficult-combustible

Combustible

Roofload-bearingelements

1.501.00

0.50

NoncombustibleNoncombustibleNoncombustible

ExitstairCombustible

1.501.000.75

Noncombustible

Difficult-combustibleDifficult-combustible

Suspendedceiling(includingceilingjoist)Combustible

0.25

0.250.15

Note:AsforthesuspendedceilingmadeofnoncombustiblematerialsinbuildingswithClassⅡfireresistance,itsfire-resistanceratingis

notrequired.

·7·3.2.2Thefire-resistanceclassofhigh-risefactorybuildingsandClassAandBfactorybuildings

shallbeatleastClassⅡ.Independentsingle-storeyClassAandBfactorybuildingswithbuilding

2

areanotgreaterthan300mmaybeClassⅢ.

3.2.3Thefire-resistanceclassshallbenotlessthanClassⅢforsingle-/multi-storeyClassC

factorybuildingsandmulti-storeyClassDandEfactorybuildings.

Thefire-resistanceclassshallbenotlessthanClassⅡforfactorybuildingswhereClassC

liquidsareusedorgenerated,andClassDfactorybuildingswherespark,red-hotsubjectsoropen

flamearepresent.Thefire-resistanceclassmaybeClassⅢforsingle-storeyClassCfactory

2

buildingswithbuildingareanotgreaterthan500morsingle-storeyClassDfactorybuildingswith

2

buildingareanotgreaterthan1000m.

3.2.4Thefire-resistanceclassshallbenotlessthanClassⅡforbuildingswhereparticularly

valuableequipmentorarticlessuchasmachinery,instrumentsandapparatusesareinstalledor

stored.

3.2.5Fire-resistanceclassshallbenotlessthanClassⅡforboilerroom.Incaseofcoal-firedboiler

roomwithtotalevaporationcapacitynotgreaterthan4t/h,thefire-resistanceclassmaybeClassⅢ.

3.2.6Fire-resistanceclassshallbenotlessthanClassⅡforoil-immersedtransformerroomandhigh-

voltagedistributionsubstation.Theotherfireprotectiondesignshallcomplywiththerequirementsof

currentnationalstandardslikeGB50229StandardforDesignofFireProtectionforFossilFuelPower

PlantsandSubstationsetc.

3.2.7Fire-resistanceclassshallbenotlessthanClassⅡforhighrackstorages,high-rise

storages,ClassAstorages,multi-storeyClassBstorages,multi-storeyClassCstoragesstoring

combustibleliquid.

Fire-resistanceclassshallbenotlessthanClassⅢforsingle-storeyClassBstorages,single-

storeyClassCstorages,multi-storeyClassCstoragesstoringcombustiblesolidsandmulti-storey

ClassDandEstorages.

3.2.8Fire-resistanceclassofgrainsilosshallbenotlessthanClassⅡ;ClassⅡgrainsilocanbe

constructedwithsteel.

Fire-resistanceclassofgrainstorehousesshallbenotlessthanClassⅢ;unprotectedmetalload-

bearingelementscanbeusedforClassⅡbulkgrainstorehouses.

3.2.9Fire-resistanceratingoffirewallsshallbenotlessthan4.00hforClassAandBfactory

buildingsandClassA,BandCstorages.

3.2.10Fire-resistanceratingofcolumnsshallbenotlessthan2.50hand2.00hrespectivelyforClass

ⅠorClassⅡsingle-storeyfactorybuildings(storages).

3.2.11Fire-resistanceratingofroofload-bearingelementsshallbenotlessthan1.00hforClassⅠ

single-/multi-storeyfactorybuildings(storages)fullyprotectedbysprinklersystem.

3.2.12FornonbearingexteriorwallofClassⅠandClassⅡbuildings,otherthanClassAandB

storagesandhigh-risestorages,whenitisnoncombustible,thefire-resistanceratingshallbenotless

than0.25h;whenitisdifficult-combustible,thefire-resistanceratingshallbenotlessthan0.50h.

Thefire-resistanceratingofthenonbearingexteriorwallisnotrequiredforClassDandEfactory

building(storage),providedthatthefire-resistanceclassofthebuildingisClassⅠorClassⅡ

buildings,theheightofthebuildingis4storeysorless,andnonbearingexteriorwallsare

noncombustible.

·8·3.2.13WhentheroompartitionwallofClassⅡfactorybuildings(storages)isdifficult-combustible,its

fire-resistanceratingshallbeincreasedby0.25h.

3.2.14Whenpre-stressedreinforcedconcretefloorslabisusedinClassⅡmulti-storeyfactory

buildingsandstorages,itsfire-resistanceratingshallbenotlessthan0.75h.

3.2.15FortheaccessibleflatroofofClassⅠorClassⅡfactorybuildings(storages),thefire-

resistanceratingoftheroofslabshallbenotlessthan1.50hand1.00hrespectively.

3.2.16RoofslabofClassⅠorClassⅡfactorybuildings(storages)shallbenoncombustible.

Roofwaterbarriershouldbenoncombustibleordifficult-combustible.Whencombustiblewater

barrierisusedandlaidoncombustibleordifficult-combustiblethermalinsulationmaterials,thewater

barrierorthecombustible,difficult-combustiblethermalinsulationmaterialsshallbeprotectedwith

noncombustiblematerials.

3.2.17Ifitisnecessarytousemetalsandwichboardasnonbearingexteriorwall,roompartitionwallor

roofslab,thecorematerialshallbenoncombustibleanditsfire-resistanceratingshallcomplywiththe

relevantrequirementsofthiscode.

3.2.18Unlessotherwiserequiredbyprovisionsofthiscode,thefire-resistanceclassmaybeclassified

asClassⅣforfactorybuildings(storages)withload-bearingwoodencolumnsandnoncombustible

walls.

3.2.19Fireprotectionmeasuresshallbetakenfortheexposedjointsofprecastreinforcedconcrete

elements,andthefire-resistanceratingofthejointsshallbenotlessthanthatofthecorresponding

elements.

3.3Storeys,areasandplanearrangementoffactorybuildingsandstorages

3.3.1Unlessotherwiserequiredbyprovisionsofthiscode,thenumberofstoreysoffactory

buildingsandthemaximumpermissiblegrossfloorareaofeachfirecompartmentshallbein

accordancewiththosespecifiedinTable3.3.1.

Table3.3.1Numberofstoreysoffactorybuildingsandmaximum

permissiblegrossfloorareaofeachfirecompartment

2

Maximumpermissiblegrossfloorareaofeachfirecompartment(m)

Maximum

Undergroundorsemi-

Firehazard

Fire-resistance

permissible

undergroundfactory

classification

classoffactory

Single-storeyMulti-storeyHigh-rise

numberof

building(including

ofproduction

building

factorybuildingfactorybuildingfactorybuilding

storeys

basementandsemi-

basement)

ClassⅠPreferably40003000----

A

ClassⅡSinglestorey30002000----

ClassⅠUnlimited500040002000--

B

ClassⅡ6400030001500--

ClassⅠUnlimitedUnlimited60003000500

CClassⅡUnlimited800040002000500

ClassⅢ230002000----

·9·Table3.3.1(continued)

2

Maximumpermissiblegrossfloorareaofeachfirecompartment(m)

Maximum

Undergroundorsemi-

FirehazardFire-resistance

permissible

undergroundfactory

classification

classoffactory

Single-storeyMulti-storeyHigh-rise

numberof

building(including

ofproduction

building

factorybuildingfactorybuildingfactorybuilding

storeys

basementandsemi-

basement)

ClassⅠandⅡ

UnlimitedUnlimitedUnlimited40001000

DClassⅢ340002000----

ClassⅣ11000------

ClassⅠandⅡUnlimitedUnlimitedUnlimited60001000

EClassⅢ

350003000----

ClassⅣ11500------

Notes:1Thefirecompartmentsshallbeseparatedbyfirewalls.ClassⅠorClassⅡfactorybuildingsotherthanClassAfactory

buildingmayusefireshutterorwatercurtainasfireseparationifthegrossfloorareaofitsfirecompartmentislarger

thanwhatrequiredinthistableanditisindeeddifficulttobeseparatedbyafirewall.Ifafireshutterisused,itshall

complywiththerequirementsofSection6.5.3ofthiscode;ifwatercurtainisused,itshallcomplywiththerequirements

ofthecurrentnationalstandardGB50084CodeforDesignofSprinklerSystems.

2AsforClassⅠmulti-storeytextilefactorybuildingsandClassⅡsingle-/multi-storeytextilefactorybuildingsotherthan

flaxmills,themaximumpermissiblegrossfloorareaofeachfirecompartmentmaybeincreasedby0.5timesofthose

specifiedinthistable,buttherawcottonunpackingandblowingworkshopsshallbeseparatedfromtheremainderofthe

buildingbyfirepartitionwallswithfire-resistanceratingnotlessthan2.50h;ifopeningssuchasdoors,windowsorthe

likeareprovided,theopeningsshallbeprotectedbyClassAfiredoorsorwindows.

3AsforClassⅠorⅡsingle-/multi-storeypapermillswithmultipleprocesses,themaximumpermissiblegrossfloorarea

ofeachfirecompartmentmaybeincreasedby1.5timesofthosespecifiedinthistable.AsforClassⅠorⅡwetpaper

mills,ifautomaticfireextinguishingsystemisprovidedinthedryerhoodofpapermachineandeffectivefire

extinguishingfacilitiesareprovidedatthefinishingsectionforthepurposeoffireprotection,themaximumpermissible

grossfloorareaofeachfirecompartmentmaybedeterminedaccordingtotheprocessneeds.

4Ifthenumberofworkersateachstoreydoesnotexceed2,thenumberofstoreyofClassⅠorⅡgrainsiloisnotlimited.

5TheproductionareasinClassⅠorⅡmulti-processcigarettefactorybuildingsforrawmaterial,stock,grouping

formulation,cigaretteprocessing,storingandpacking,auxiliarymaterialturnover,temporarystorageoffinished

productsandcarbondioxidedilatatetobaccoshredshallbefireseparatedfromeachother.Firewallsshallbeusedwhen

theprocessconditionspermit.However,thespacesforcigaretteprocessing,storingandpackingmaybearrangedwithin

onefirecompartment.Themaximumpermissiblegrossfloorareaofthefirecompartmentmaybedeterminedaccording

totheneedsoftheprocess,butthespacesforcigaretteprocessing,storingandpackingshallbeseparatedby2.00hfire-

resistance-ratedpartitionwallsand1.00hfire-resistance-ratedfloors.Inaddition,propermeasuresshallbetakento

protecttheopeningsbetweenhorizontalandverticalfireseparationssoastopreventfirespreading.

6Asfortheoperationplatformandrepairplatforminfactorybuildings,iftheoccupantloadislessthan10,theplatform

areamaynotbecountedintothegrossfloorareaofthefirecompartment.

7"--"means"notpermitted".

3.3.2Unlessotherwiserequiredbyprovisionsofthiscode,thenumberofstoreysandareaof

storagesshallbeinaccordancewiththosespecifiedinTable3.3.2.

·10·

·11·

Table3.3.2Numberofstoreysandareaofstorages

2

Maximumpermissiblefirstfloorareaofeachstorageandmaximumpermissiblegrossfloorareaofeachfirecompartment(m)

Undergroundorsemi-

undergroundstorage

FirehazardMaximum

Single-storeystorageMulti-storeystorageHigh-risestorage

Fire-resistance

(includingbasementand

classificationofstoredpermissible

classofstorages

materialsnumberofstoreyssemi-basement)

FireFire

EachstorageFirecompartmentEachstorageEachstorageFirecompartment

compartmentcompartment

Item3and4ClassⅠ118060----------

A

Item1,2,5and6ClassⅠandⅡ1750250----------

ClassⅠandⅡ32000500900300------

Item1,3and4

ClassⅢ1500250----------

B

ClassⅠandⅡ528007001500500------

Item2,5and6

ClassⅢ1900300----------

ClassⅠandⅡ5400010002800700----150

Item1

----

ClassⅢ11200400------

C

ClassⅠandⅡUnlimited600015004800120040001000300

Item2

ClassⅢ321007001200400------

·12·

Table3.3.2(continued)

2

Maximumpermissiblefirstfloorareaofeachstorageandmaximumpermissiblegrossfloorareaofeachfirecompartment(m)

Undergroundorsemi-

undergroundstorage

FirehazardMaximum

Single-storeystorageMulti-storeystorageHigh-risestorage

Fire-resistance

(includingbasementand

classificationofstoredpermissible

classofstorages

materialsnumberofstoreys

semi-basement)

FireFire

EachstorageFirecompartmentEachstorageEachstorageFirecompartment

compartmentcompartment

ClassⅠandⅡUnlimitedUnlimited3000Unlimited150048001200500

DClassⅢ3300010001500500-----

ClassⅣ12100700---------

ClassⅠandⅡUnlimitedUnlimitedUnlimitedUnlimited2000600015001000

EClassⅢ3300010002100700-----

ClassⅣ12100700---------

Notes:1Firecompartmentsinthestoragesmustbeseparatedbyfirewalls.Thereshallbenoopeningslikedoors,windowsandthelikeinthefirewallsofClassAandBstorages.Themaximum

permissiblefirstfloorareaofundergroundorsemi-undergroundstorages(includingbasementandsemi-basement)shallbenotgreaterthanthatoftheabovegroundstoragesofthe

correspondingclass.

2ThebarreloilstoragesinoildepotshallcomplywiththerequirementsofthecurrentnationalstandardGB50074CodeforDesignofOilDepot.

2

3ForClassⅠ,Ⅱcoalhomogenizationsilo,themaximumpermissiblegrossfloorareaofeachfirecompartmentshallbenotgreaterthan12000m.

4Forindependentlybuiltammoniumnitratestorages,calciumcarbidestorages,thestoragesofmoleculeproductssuchaspolyethylene,ureastorages,blendedcoalstorages,independent

finishedproductstoragesofpapermill,whenthefire-resistanceclassofthebuildingisnotlessthanClassⅡ,themaximumpermissiblefirstfloorareaofeachstorageandthemaximum

permissiblegrossfloorareaofeachfirecompartmentmaybeincreasedby1.0timesofthosespecifiedinthistable.

2

5ThemaximumpermissiblefirstfloorareaofClassⅠorⅡgrainstorehouseshallbenotgreaterthan12000m,andthemaximumpermissiblegrossfloorareaofeachfirecompartmentshall

22

benotgreaterthan3000m;themaximumpermissiblefirstfloorareaofClassⅢgrainstorehouseshallbenotgreaterthan3000m,andthemaximumpermissiblegrossfloorareaofeach

2

firecompartmentshallbenotgreaterthan1000m.

2

6ForClassⅠorⅡsingle-storeycottonwarehousewithfirstfloorareanotgreaterthan2000m,themaximumpermissiblegrossfloorareaofeachfirecompartmentshallbenotgreaterthan

2

2000m.

7ThemaximumpermissiblefirstfloorareaofClassⅠorⅡcoldstoreanditsmaximumpermissiblegrossfloorareaoffirecompartmentshallcomplywiththerequirementsofthecurrent

nationalstandardGB50072CodeforDesignofColdStore.

8"--"means"notpermitted".3.3.3Whereautomaticfireextinguishingsystemisprovidedinfactorybuildings,themaximum

permissiblegrossfloorareaofeachfirecompartmentmaybeincreasedby1.0timesofthosespecifiedin

Section3.3.1ofthiscode.WhereautomaticfireextinguishingsystemisprovidedinClassDandE

factorybuildings,themaximumpermissiblegrossfloorareaofeachfirecompartmentisnotlimited.

Whereautomaticfireextinguishingsystemisprovidedinpartofthefactorybuildings,onlytheareaof

thatpartcanbeincreasedby1.0times.

Whereautomaticfireextinguishingsystemisprovidedinthestorages,boththemaximum

permissiblefirstfloorareaofthestoragesandthemaximumpermissiblegrossfloorareaofeachfire

compartmentmaybeincreasedby1.0timesofthosespecifiedinSection3.3.2ofthiscode.The

maximumpermissiblegrossfloorareaofthefirecompartmentofcoldstoreshallnotbeincreasedeven

ifautomaticfireextinguishingsystemisprovided.

3.3.4Placesusing,generatingorstoringClassAandBsubstancesshallnotbepermittedin

undergroundorsemi-undergroundbuildings.

3.3.5Staffdormitorymustbestrictlyprohibitedinfactorybuildings.

OfficesandstaffloungesshallbenotpermittedinClassAandBfactorybuildings;ifoffices

andstaffloungesmustbebuiltadjoiningtothefactorybuildings,thefire-resistanceclassofthe

office(stafflounge)buildingshallbenotlessthanClassⅡ,andthecommonwallshallbe

explosion-proofwallwithfire-resistanceratingnotlessthan3.00h,anddedicatedexitsshallbe

provided.

OfficesandstaffloungeslocatedinClassCfactorybuildingsshallbeseparatedfromthe

remainderofthebuildingbyfirepartitionwallswithfire-resistanceratingnotlessthan2.50hand

floorwithfire-resistanceratingnotlessthan1.00h,andatleast1dedicatedexitshallbeprovided.

DoorsinthefirepartitionwallshallbeClassBfiredoors.

3.3.6Intermediatestorageslocatedinfactorybuildingsshallcomplywiththefollowing

requirements:

1ClassAorBintermediatestoragesshallbeclosetotheexternalwalls,thestoragecapacity

shouldnotexceedthedemandfor24h;

2ClassA,BandCintermediatestoragesshallbeseparatedfromtheremainderofthe

buildingbyfirewallsandnoncombustiblefloorswithfire-resistanceratingnotlessthan1.50h;

3ClassDandEintermediatestoragesshallbeseparatedfromtheremainderofthebuildingby

firepartitionwallswithfire-resistanceratingnotlessthan2.00handfloorswithfire-resistanceratingnot

lessthan1.00h;

4Thefire-resistanceclassandfirstfloorareaofstoragesshallcomplywiththerequirementsof

Article3.3.2andArticle3.3.3ofthiscode.

3.3.7ClassCintermediatetanksinthefactorybuildingsshallbearrangedinaseparatedroomandits

3

capacityshallbenotgreaterthan5m.Theroomswithintermediatetanksshallbeseparatedfromthe

remainderofthebuildingbyfirepartitionwallswithfire-resistanceratingnotlessthan3.00handfloors

withfire-resistanceratingnotlessthan1.50h,thedooroftheroomshallbeClassAfiredoor.

3.3.8Transformeranddistributionsubstationshallnotbepermittedtobeinoradjoiningto

ClassAandBfactorybuildings,andshallnotbeexposedtohazardousareascontainingexplosive

gasordust.Transformeranddistributionsubstationwithcapacityas10kVorlessdedicatedforthe

powersupplyofClassAorBfactorybuildingsmaybeadjoinedtoonlyoneexternalwallofthe

·13·factorybuilding,andthewallshallbefirewallwithoutopeningssuchasdoor,windoworthelike.

Moreover,thesubstationshallcomplywiththerequirementsofthecurrentnationalstandardGB50058

CodeforDesignofElectricalInstallationsinExplosiveAtmospheres,etc..

FordistributionsubstationdedicatedforClassBfactorybuildings,windowsinthefirewall

shallbeClassAfirewindows.

3.3.9Staffdormitorymustbestrictlyprohibitedinthestorages.

OfficesandstaffloungesmustnotbepermittedinoradjoiningtoClassAandBstorages.

WhereofficesandstaffloungesarepermittedinClassCandDstorages,theofficesandstaff

loungesshallbeseparatedfromtheremainderofthebuildingbyfirepartitionwallwithfire-

resistanceratingnotlessthan2.50handfloorwithfire-resistanceratingnotlessthan1.00h,and

dedicatedexitshallbeprovided.Whereitisnecessarytoprovidedoorsinthepartitionwall,Class

Bfiredoorsshallbeinstalled.

3.3.10Fireprotectiondesignoflogisticsbuildingsshallcomplywiththefollowingrequirements:

1Wherethemainfunctionofthebuildingissortingorprocessing,thefireprotectiondesignshall

complywiththerelevantrequirementsoffactorybuildingsofthiscode;thestoragepartshallcomply

withtherequirementsforintermediatestorages.

2Wherethemainfunctionofthebuildingisstorageoritisdifficulttodistinguishitsmain

function,thefireprotectiondesignshallcomplywiththerelevantrequirementsofstoragesofthiscode.

However,wheretheoperatingareassuchassortingareaarecompletelyseparatedfromstorageareas,

thefireprotectionrequirementsofoperatingareasmaycomplywiththerelevantrequirementsoffactory

buildingsandstorageareasmaycomplywiththerequirementsofstoragesofthiscode.

Wheretheoperatingareassuchassortingareaarecompletelyseparatedfromthestorageareasby

firewall,andwhenthefollowingconditionsaremet,exceptClassChighrackstorageswithautomatic

control,themaximumpermissiblegrossfloorareaofthefirecompartmentsinthestorageareaandthe

maximumpermissiblefirstfloorareaofthestoragemaybeincreasedby3.0timesoftherequirements

specifiedinTable3.3.2(notincludethenotes)ofthiscode:

1)StoringClassCmaterialsexceptcombustibleliquid,cotton,linen,silk,woolandother

textiles,foamplastic,andthefire-resistanceclassofthebuildingisnotlessthanClassⅠ;

2)StoringClassDandEmaterialsandthefire-resistanceclassofthebuildingisnotlessthan

ClassⅡ;

3)Thewholebuildingisprotectedbyautomaticwaterfireextinguishingsystemsandfirealarm

systems.

3.3.11NorailwaylineshallbepermittedinClassAandBfactorybuildings(storages).

ForClassC,DandEfactorybuildings(storages),wheresteamordiesellocomotivesare

permittedtoaccess,theroofshallbenoncombustibleorfireprotectedbyothermeans.

3.4Fireseparationdistanceoffactorybuildings

3.4.1Unlessotherwiserequiredbyprovisionsofthiscode,thefireseparationdistancebetween

anytwofactorybuildings,betweenanyfactorybuildingsandanyClassB,C,DandEstorages,

betweenanyfactorybuildingsandcivilbuildingsetc.shallbenotlessthanthosespecifiedinTable

3.4.1.FireseparationdistancebetweenfactorybuildingandClassAstorageshallcomplywith

thosespecifiedinArticle3.5.1ofthiscode.

·14·

·15·

Table3.4.1Fireseparationdistancebetweenanytwofactorybuildings,factorybuildings

andClassB,C,DandEstorages,factorybuildingsandcivilbuildings(m)

ClassAfactoryClassBfactorybuildingsClassC,DandEfactorybuildings

Civilbuildings

buildings(storages)(storages)

Single/multi-Single-/multi-High-Podiumandsingle-/multi-

Single-/multi-storeyHigh-riseHigh-rise

Name

storeystoreyrisestorey

ClassⅠClassⅠClassClassⅠClassⅠClassⅠClassⅠ

ClassⅢClassⅣClassⅢClassⅣClassⅠClassⅡ

andⅡandⅡⅢandⅡandⅡandⅡandⅡ

ClassAfactory

Single-/multi-

ClassⅠandⅡ1212141312141613

buildings

storey

ClassⅠandⅡ1210121310121413

Single-/multi-2550

ClassBfactory

storey

ClassⅢ1412141512141615

buildings

ClassⅠandⅡ1313151313151713

High-rise

ClassⅠandⅡ1210121310121413101214

2015

Single-/multi-

ClassⅢ1412141512141615121416

ClassCfactory

storey

2520

buildings

ClassⅣ161416171416181714

1618

ClassⅠandⅡ13131513131517131315172015

High-rise

ClassⅠandⅡ1210121310121413

1012141513

Single-/multi-

ClassDandE

ClassⅢ1412141512141615121416

storey

factory

1815

ClassⅣ16141617141618

buildings17141618

ClassⅠandⅡ13131513131517131315171513

High-rise

·16·

Table3.4.1(continued)

ClassAfactoryClassBfactorybuildingsClassC,DandEfactorybuildings

Civilbuildings

buildings(storages)(storages)

Single/multi-Single-/multi-High-Podiumandsingle-/multi-

Single-/multi-storeyHigh-riseHigh-rise

Name

storeystoreyrisestorey

ClassⅠClassⅠClassClassⅠClassⅠClassⅠClassⅠ

ClassⅢClassⅣClassⅢClassⅣClassⅠClassⅡ

andⅡandⅡⅢandⅡandⅡandⅡandⅡ

Outdoor

≥5,≤101215201215202520

transformerandTotaloilmassof

25252525

>10,≤501520251520253025

distributiontransformer(t)

substation

>502025302025303530

Notes:1FireseparationdistancebetweenClassBfactorybuildingsandimportantpublicbuildingsshouldnotbelessthan50m;fireseparationdistancebetweenClassBfactorybuildingsand

openflameorsparkingsiteshouldnotbelessthan30m.Fireseparationdistancebetweensingle-/multi-storeyClassEfactorybuildings,ClassEfactorybuildingsandClassEstorages

maybereducedby2mbasedonthosespecifiedinthistable.Fireseparationdistancebetweensingle-/multi-storeyClassEfactorybuildingsandcivilbuildingsmaytakeClassEfactory

buildingsascivilbuildingsandthenbedeterminedaccordingtotherequirementsof5.2.2ofthiscode.TheseparatelivingareaprovidedforClassC,DandEfactorybuildingsshallbe

designedaccordingtotherequirementsforcivilbuildings.Fireseparationdistancebetweenthelivingareasandthefactorybuildingsshallbenotlessthan6m.Ifitisreallynecessaryto

beadjacent,itshallcomplywiththerequirementsofNote2andNote3ofthistable.

2Whenthehigherexteriorwalloftwoadjacentfactorybuildingsisafirewall,oranyoftheexteriorwallsoftwoadjacentClassⅠorClassⅡbuildingswiththesameheightisafirewall

andthefire-resistanceratingoftheroofisnotlessthan1.00h,thefireseparationdistanceisnotlimited,butthedistancebetweenClassAfactorybuildingsmeetingtheaboveconditions

shallbenotlessthan4m.IftwoadjacentexteriorwallsoftwoClassC,DandEfactorybuildingsarenoncombustible,thesumoftheareaofopeningslikedoor,windoworthelikein

eachwallshallbenotgreaterthan5%oftheexteriorwallarea,thereisnoexposedcombustibleeave,andthedoor,windoworotheropeningsinthetwoadjacentwallsarenotright

oppositetoeachother,thenthefireseparationdistancemaybereducedby25%basedonthosespecifiedinthistable.ClassAandBfactorybuildings(storages)shallnotbeadjoining

withthebuildingsnotspecifiedinArticle3.3.5ofthiscode.

3FortwofactorybuildingswithClassⅠ,Ⅱfire-resistanceclass,wherethelowerexteriorwallisafirewallandtheroofofthelowerfactorybuildinghasnoskylightandfire-resistance

ratingoftheroofisnotlessthan1.00h,orClassAfiredoorandwindoworwatercurtainareprovidedfortheopeningsofdoorandwindowinthehigherexteriorwallorfireshutteris

providedforthemaccordingtotherequirementsofArticle6.5.3ofthiscode,thefireseparationdistancebetweenClassAandBfactorybuildingsshallbenotlessthan6m,andnotbe

lessthan4mforClassC,DandEfactorybuildings.

4Thetotaloilamountofmaintransformerinthepowerplantmaybedeterminedbyoneset.

5Fire-resistanceclassoftheexistingfactorybuildingswiththefire-resistanceclasslowerthanⅣmaybedeemedasClassⅣ.

6WhereClassC,DandEfactorybuildingsareadjacenttoClassC,DandEstorages,itshallcomplywiththerequirementsofNote2andNote3ofthistable.3.4.2FireseparationdistancebetweenClassAfactorybuildingandimportantpublicbuilding

shallbenotlessthan50m,andshallbeatleast30mawayfromopenflameorsparkingsite.

3.4.3FireseparationdistancebetweenClassAfactorybuildingswithcombustiblegasorvaporand

railwayorroadshallbenotlessthanthosespecifiedinTable3.4.3.However,ifsafetymeasuresare

takenfortheloadingandunloadinglinesoftherailwayinClassAfactorybuildings,theirfireseparation

distancemaynotbelimitedbythosespecifiedinTable3.4.3.

Table3.4.3FireseparationdistancebetweenClassAfactorybuildingswith

combustiblegasorvaporandrailwayorroad(m)

In-factoryroadside

Centerlineofoff-factoryCenterlineofin-factory

Name

Off-factoryroadside

railwayrailway

PrimarySecondary

ClassAfactorybuilding302015105

3.4.4Fireseparationdistancebetweenhigh-risefactorybuildingandClassA,B,Cliquidtank,

combustibleandcombustion-supportinggastank,LPGtank,stackyardforcombustibles(except

coalandcokeyards)shallcomplywiththerequirementsofChapter4ofthiscode,andshallbenot

lessthan13m.

3.4.5Wherethefire-resistanceclassofClassC,DandEfactorybuildingandcivilbuildingisClassⅠ

orClassⅡ,thefireseparationdistancebetweenthefactorybuildingandcivilbuildingmaybereduced

tosomeextent,butshallcomplywiththefollowingrequirements:

1Wherethehigherexteriorwallisafirewallwithoutdoor,windoworotheropenings,orthe

exteriorwallwithin15mhigherthantheroofingoftheadjacentlowerbuildingandthepartofthe

exteriorwallbelowisfirewallwithoutdoor,windoworotheropenings,thefireseparationdistanceis

notlimited;

2Iftheadjacentlowerexteriorwallisfirewallandtheroofhasnoskylightoropeningandthe

fire-resistanceratingofroofisnotlessthan1.00h,ortheadjacenthigherexteriorwallisfirewallandthe

openinginthewallisproperlyfireprotected,thefireseparationdistancemaybereduced,butshallbe

notlessthan4m.

3.4.6Ifequipmentforchemicalflammablesisprovidedoutsidethefactorybuilding,thefireseparation

distancebetweentheoutersurfaceoftheequipmentandtheoutersurfaceofauxiliaryequipmentofthe

adjacentfactorybuildingortheexteriorwalloftheadjacentfactorybuildingshallbenotlessthanthose

specifiedinArticle3.4.1ofthiscode.Theoutdoorequipmentmadeofnoncombustiblematerialsmay

beregardedasClassⅠorClassⅡbuildingwhendeterminingthefireseparationdistance.

3

IfClassCliquidtankwiththetotalvolumenotgreaterthan15misdirectlyburiedoutsidethe

exteriorwallofthefactorybuildingandtheexteriorwallwithin4.0mfromthetankisfirewall,thefire

separationdistanceisnotlimited.

3.4.7FireseparationdistancebetweentwoadjacentwingsofaU-shapedorW-shapedfactory

buildingshouldnotbelessthanthosespecifiedinArticle3.4.1ofthiscode.However,wherethefirst

floorareaofthefactorybuildingislessthanthemaximumpermissiblegrossfloorareaofeachfire

compartmentspecifiedinArticle3.3.1ofthiscode,thefireseparationdistancemaybenotlessthan

6m.

3.4.8Excepthigh-risefactorybuildingsandClassAfactorybuildings,wherethesumofthefirstfloor

areaofseveralfactorybuildingsislessthanthemaximumpermissiblegrossfloorareaofthefire

·17·compartmentspecifiedinArticle3.3.1ofthiscode(themaximumpermissiblegrossfloorareaoffire

2

compartmentshallbedeterminedaccordingtothesmallerone,butshallbenotgreaterthan10000mif

itisnotlimited),thesefactorybuildingsmaybearrangedbygroup.Wheretheheightoffactory

buildingsisnotgreaterthan7m,thefireseparationdistancebetweenfactorybuildingswithinagroup

shallbenotlessthan4m;otherwisethedistanceshallbenotlessthan6m.

Fireseparationdistancebetweengroupsorbetweenthegroupandadjacentbuildingsshallbe

determinedbasedontheonewithlowerfire-resistanceclassintwoadjacentbuildingsandthose

specifiedinArticle3.4.1ofthiscode.

3.4.9ClassⅠmotorgasand/orgasolinedispensingstationshallnotbelocatedinurbanbuilt-up

areas.

3.4.10Theclassificationofmotorgasand/orgasolinedispensingstation,thefireseparationdistance

frommotorgasand/orgasolinedispensingstationaswellasthegasoline(gas)dispenser,gasoline(gas)

tanktooff-stationopenflamelocation,sparkingsite,building,railwayorroad,andthefireseparation

distancebetweenin-stationbuildingsorfacilities,shallcomplywiththerequirementsofthecurrent

nationalstandardGB50156CodeforDesignandConstructionofFillingStation.

3.4.11Fireseparationdistancefromtheoutdoortransformeranddistributionsubstationwiththe

voltageof35kV-500kVandthecapacityofeachtransformernotlessthan10MV·A,theoutdoorstep-

downsubstationswiththetotaloilamountoftransformersforindustrialenterprisesgreaterthan5tto

theotherbuildingsshallbenotlessthanthosespecifiedinArticle3.4.1andArticle3.5.1ofthiscode,

respectively.

3.4.12Thedistancebetweentheboundingwallofthefactoryandthebuildingsinthefactoryshould

notbelessthan5m.Thedistancebetweentwobuildingsoneachsideofaboundingwallshallcomply

withthefireseparationdistancerequirementsforcorrespondingbuildings.

3.5Fireseparationdistanceofstorages

3.5.1FireseparationdistancebetweenanytwoClassAstorages,ClassAstorageandother

building,openflamelocationorsparkingsite,railway,roadetc.shallbenotlessthanthose

specifiedinTable3.5.1.

Table3.5.1Fireseparationdistance(m)betweenanytwoClassAstorages,ClassAstorageandother

building,openflamelocationorsparkingsite,railway,roadetc(.m)

ClassAstorage(storagecapacity,t)

ClassAstoredmaterialsClassAstoredmaterials

Name

Item3and4Item1,2,5,and6

≤5>5≤10>10

High-risecivilbuildingsandimportantpublicbuildings50

Podium,othercivilbuildings,openflamelocationsorsparking

30402530

sites

ClassAstorages20202020

ClassⅠandⅡ15201215

FactorybuildingsandClassB,

ClassⅢ20251520

C,DandEstorages

ClassⅣ25302025

·18·Table3.5.1(continued)

ClassAstorage(storagecapacity,t)

ClassAstoredmaterialsClassAstoredmaterials

Name

Item3and4Item1,2,5,and6

≤5>5≤10>10

Outdoortransformeranddistributionsubstationwiththe

voltageof35kVto500kVandthecapacityofeachtransformer

30402530

notlessthan10MV·A,outdoorstep-downelectricpower

substationswiththetotaloilamountoftransformersfor

industrialenterprisesgreaterthan5t

40

Centerlineofoff-factoryrailway

30

Centerlineofin-factoryrailway

20

Off-factoryroadside

Primary10

In-factoryroadside

Secondary5

Note:WherethestoragecapacityofItem3or4isnotgreaterthan2tandthestoragecapacityofItem1,2,5and6isnotgreater

than5t,thefireseparationdistancebetweensuchClassAstoragesshallbenotlessthan12mandthefireseparationdistance

betweensuchClassAstorageandhigh-risestorageshallbenotlessthan13m.

3.5.2Unlessotherwiserequiredbyprovisionsofthiscode,thefireseparationdistancebetween

anytwoClassB,C,D,Estorages,andbetweenanyClassB,C,D,Estoragesandanycivilbuildings

shallbenotlessthanthosespecifiedinTable3.5.2.

Table3.5.2Fireseparationdistance(m)betweenClassB,C,DandEstorages,Class

B,C,DandEstoragesandcivilbuildings(m)

ClassBstorageClassCstorageClassDandEstorage

Single-/multi-High-

High-riseSingle-/multi-storeySingle-/multi-storeyHigh-rise

storeyrise

Name

ClassⅠClassⅠClassⅠClassClassClassⅠClassClassClassClassⅠ

ClassⅢ

andⅡandⅡandⅡⅢⅣandⅡⅠ,ⅡⅢⅣandⅡ

ClassⅠ

1012131012141310121413

andⅡ

ClassB,C,Single-/

DandEClassⅢ1214151214161512141615

multi-

storage

storey

ClassⅣ1416171416181714161817

·19·Table3.5.2(continued)

ClassBstorageClassCstorageClassDandEstorage

Single-/multi-High-

High-riseSingle-/multi-storeySingle-/multi-storeyHigh-rise

storeyrise

Name

ClassⅠClassⅠClassⅠClassClassClassⅠClassClassClassClassⅠ

ClassⅢ

andⅡandⅡandⅡⅢⅣandⅡⅠ,ⅡⅢⅣandⅡ

ClassB,C,

ClassⅠ

High-

DandE

1315131315171313151713

andⅡ

rise

storage

PodiumClassⅠ

1012141310121413

and

andⅡ

single-/

25

ClassⅢ1214161512141615

Civilmulti-

buildingstorey

ClassⅣ1416181714161817

ClassⅠ2025252015181815

High-

50

rise

ClassⅡ1520201513151513

Notes:1Fireseparationdistancebetweensingle-/multi-storeyClassEstoragesmaybereducedby2mbasedonthosespecifiedin

thistable.

2Wheretheadjacentexternalwallsoftwostoragesarebothfirewalls,thefireseparationdistancemaybereduced,butit

shallbenotlessthan6mforClassCstorages,and4mforClassDandEstorages.Wheretheadjacenthigherexterior

wallsoftwostoragesarefirewalls,orwheretheexternalwallonanysideoftwoadjacentClassⅠⅠ,ⅡⅡbuildingswiththe

sameheightisafirewallandthefire-resistanceratingoftheroofisnotlessthan1.00h,andwherethetotalfirstfloor

areaisnotgreaterthanthemaximumpermissiblefirstfloorareaofastoragerequiredinSection3.3.2ofthiscode,the

fireseparationdistanceisnotlimited.

3ThefireseparationdistancefromClassBstorages(exceptthoseforClassBItem6articles)tocivilbuildingsshould

notbelessthan25m,andshallbenotlessthan50mtoimportantpublicbuildings.Thefireseparationdistanceto

railway,roadetc.shouldnotbelessthanthosebetweenClassAstoragesandrailway,roadetc.asspecifiedinTable

3.5.1.

3.5.3Wherethefire-resistanceclassofClassDandEstoragesandcivilbuildingsareClassⅠorⅡ,

thefireseparationdistancebetweenstoragesandcivilbuildingsmaybereduced,butshallcomplywith

thefollowingrequirements:

1Thefireseparationdistanceisnotlimited,providedthatthehigherexteriorwallisafirewall

withoutdoor,windoworotheropenings,ortheexteriorwallwithin15mhigherthantheroofofthe

adjacentlowerbuildingandthepartoftheexteriorwallbelowisafirewallwithoutdoor,windowor

otheropenings;

2Thefireseparationdistancemaybereducedbutshallbenotlessthan4m,providedthatthe

adjacentlowerexteriorwallisafirewall,theroofhasnoskylightoropeningandthefire-resistance

ratingoftheroofisnotlessthan1.00h,ortheadjacenthigherexteriorwallisafirewallandtheopening

inthewallisproperlyfireprotected.

3.5.4Fireseparationdistancebetweenanygrainsilosandotherbuildings,betweenanytwograinsilo

groupsshallbenotlessthanthosespecifiedinTable3.5.4.

·20·Table3.5.4Fireseparationdistancebetweenanygrainsilosandotherbuildings

andbetweenanytwograinsilogroups(m)

GrainsiloGrainsquatsiloOtherbuilding

Totalstored

Namequantityofgrains

W≤40000<

W>50000W≤50000W>50000ClassⅠ,ⅡClassⅢClassⅣ

W(t)

40000W≤50000

500<W≤10000101520

15

10000<W≤

1520

25

40000

20252025

Grainsilo

40000<W≤

20202530

50000

W>50000252530

-

W≤5000020202520252025

-

Grain

squatsilo

W>50000252530

-

Notes:1Wheregrainsilo,grainsquatsilo,operationtower,receivingtoweranddistributionstationareanintegralprocessunit,thefire

separationdistancebetweenbuildingswithintheunitdoesn'tneedtofollowthosespecifiedinthistable.

2Thestoredquantityofeachindependentsilointhegrainsquatsiloclustershallbenotgreaterthan10000t.

3.5.5Thedistancebetweentheboundingwallofthestorageareaandthebuildingsinthestoragearea

shouldnotbelessthan5m.Thedistancebetweentwobuildingsoneachsideofaboundingwallshall

complywiththefireseparationdistancerequirementsforcorrespondingbuildings.

3.6Explosionpreventionoffactorybuildingsandstorages

3.6.1ClassAandClassBfactorybuildingswithexplosionhazardshouldbebuiltindependently,and

shouldbeunenclosedorpartiallyenclosed.Theload-bearingstructureshouldbereinforcedconcrete,

steelorbentframestructure.

3.6.2Pressurereliefshallbeprovidedforfactorybuildingswithexplosionhazardoranypart

withexplosionhazardinafactorybuilding.

3.6.3Theareasforpressurereliefshouldbedoors,windows,light-weightedroofslabsorwalls.

Materialsthatmaybreakintosharpfragmentsinexplosionshallnotbeused.

Theareasforpressurereliefshallbeawayfromassemblyplacesormainroads,andshouldbe

closetospaceswithexplosionhazard.

Thedensityoflight-weightedroofslabsorwallsusedastheareaofpressurereliefshouldbeless

2

than60kg/m.

Measuresshallbetakenfortheareaofpressurereliefontherooftoavoidiceandsnow

accumulation.

3.6.4Pressurereliefareaintheroofsorwallsoffactorybuildingsshouldbecalculatedaccordingtothe

followingequation.However,wherethelength-diameterratioofafactorybuildingisgreaterthan3,the

buildingshouldbedividedintoseveralcalculatedsectionwiththelength-diameterrationotgreaterthan

3.Thecross-sectionbetweentwocalculatedsectionshallnotbeusedasthepressurereliefarea:

2

3(3.6.4)

A=10CV

2

where,A—Pressurereliefarea(m);

3

V—Volumeofthecalculatedsectioninthefactorybuilding(m);

23

C—Pressurereliefratio,giveninTable3.6.4(m/m).

·21·Table3.6.4Classificationofsubstanceswithexplosionhazardinfactorybuildings

23

andtheminimumpressurereliefratio(m/m)

ClassificationofsubstanceswithexplosionhazardinfactorybuildingsC

-1

Ammonia,grain,paper,leather,lead,chromiumandcopperetc.withK<10MPa·m·s≥0.030

dust

-1-1

Woodchip,carbondust,pulverizedcoal,stibiumandtinetc.with10MPa·m·s≤K≤30MPa·m·s≥0.055

dust

Acetone,gasoline,methanol,LPG,methane,paintsprayordryingroom,phenolresin,aluminium,

≥0.110

-1

magnesiumandzirconiumetc.withK>30MPa·m·s

dust

Ethylene≥0.160

Acetylene≥0.200

Hydrogen≥0.250

Notes:1Thelength-diameterratio=longestdimensionofthebuildingplane×theperimeterofitscross-section÷(4.0×thecalculated

cross-sectionareaofthebuilding).

2K,thedustexplosionindex.

dust

3.6.5WhereairinsidetheClassAfactorybuildingscontainscombustiblegasorvapor,whosedensity

islessthanthatofair,thelight-weightedroofslabshouldberegardedastheareaforpressurerelief;the

ceilingshallbeflatandsmoothwithoutdeadcorner;theupperspaceofthefactorybuildingsshallbe

wellventilated.

3.6.6TheClassAfactorybuildingswithairinsidecontainingcombustiblegasorvapor,whose

densityismorethanthatofair,andClassBfactorybuildingswithexplosionhazardofdustand

fibershallcomplywiththefollowingrequirements:

1Spark-freefloorshallbeprovided.Whereinsulatingmaterialsareusedasmonolithicfloor

surface,electrostaticprotectionmeasuresshallbetaken.

2Wherethefactorybuildingsgeneratecombustibledustorfiber,theinteriorsurfaceshall

beflat,smoothandeasyforcleaning.

3Trenchshouldnotbeprovidedinthefactorybuildings.Iftrenchmustbeprovided,its

covershallbetightandeffectivemeasuresshallbetakentopreventcombustiblegas,vapor,dust,

fiberfromaccumulatinginthetrench.Inaddition,firestoppingshallbeusedtosealthe

connectionbetweentrenchandadjacentfactorybuildings.

3.6.7ClassAandBproductionpartswithexplosionhazardshouldbearrangedclosetotheareafor

pressurereliefintheexteriorwallforsingle-storeyfactorybuildingsorintheexteriorwallofthetop

storeyformulti-storeyfactorybuildings.

Theequipmentwithexplosionhazardshouldbeinstalledawayfromtheprimaryload-bearing

elementsoffactorybuildings,suchasbeamsandcolumnsetc.

3.6.8ThecentralcontrolroomofClassAandBfactorybuildingswithexplosionhazardshallbe

builtindependentlyoutsidethefactorybuildings.

3.6.9Thesub-controlroomsofClassAandBfactorybuildingswithexplosionhazardshouldbebuilt

independentlyoutsidethefactorybuildings.Ifsuchroomsareadjoiningtotheexteriorwallsofthe

factorybuildings,firepartitionwallswithfire-resistanceratingnotlessthan3.00hshallbeusedto

separatesuchroomsfromotherportionsofthebuilding.

·22·3.6.10Protectivemeasures,likeavestibule,shallbetakenforstaircases,outdoorstairwaysinareas

withexplosionhazardorconnectingpartbetweenareaswithexplosionhazardandadjoiningareas.The

partitionwallsofthevestibuleshallbefireratedandthefire-resistanceratingshallbenotlessthan

2.00h;doorsofthevestibuleshallbeClassAfiredoorsandshallnotbeplacedattherightoppositeof

thedoorleadingtothestaircase.

3.6.11ForfactorybuildingsusingandgeneratingClassA,BandCliquids,thepipesand

trenchesshallnotbeconnectedwiththoseofadjacentfactorybuildings.Greasetrapsand

separatorsshallbeprovidedforthesewers.

3.6.12ThestoragesforClassA,BandCliquidsshallbeprovidedwithfacilitiestopreventliquid

fromdispersion.Storagescontainingmaterialswithcombustionorexplosionhazardinhumid

environmentshallbeprotectedwithwaterproofmeasures.

3.6.13Thecovershallbeprovidedwithproperpressurerelieffacilitiesforsiloswithdustexplosion

hazard.

Pressurereliefareaoftheoperationtowerandupperconnectingcorridoringrainsiloshallbe

calculatedaccordingtoArticle3.6.4ofthiscode.Explosionpreventionmeasuresshallbetakenfor

othergrainstorageswithdustexplosionhazard.

3.6.14Storagesorportionsthereofwithexplosionhazard,explosionpreventionmeasuresshouldbe

takenandpressurerelieffacilitiesshallbeprovidedaccordingtotherequirementsofthissection.

3.7Evacuationoffactorybuildings

3.7.1Exitsoffactorybuildingsshallbeseparatedfromeachother.Foreachfirecompartmentoreach

floorinafirecompartment,thedistancebetweenanytwoadjacentexitsshallbenotlessthan5m.

3.7.2Foreachfirecompartmentinfactorybuildingsoreachfloorinafirecompartment,the

numberofexitsshallbedeterminedbycalculationandshallbenotlessthan2;incasethefollowing

conditionsaremet,1exitispermitted:

2

1ForClassAfactorybuilding,thegrossfloorareaofeachfloorisnotgreaterthan100m

andtheoccupantloadatthesametimeisnotmorethan5;

2

2ForClassBfactorybuilding,thegrossfloorareaofeachfloorisnotgreaterthan150m

andtheoccupantloadatthesametimeisnotmorethan10;

2

3ForClassCfactorybuilding,thegrossfloorareaofeachfloorisnotgreaterthan250m

andtheoccupantloadatthesametimeisnotmorethan20;

4ForClassDandEfactorybuilding,thegrossfloorareaofeachfloorisnotgreaterthan

2

400mandtheoccupantloadatthesametimeisnotmorethan30;

5Forundergroundorsemi-undergroundfactorybuildings(includingbasementandsemi-

2

basement),thegrossfloorareaofeachfloorisnotgreaterthan50mandtheoccupantloadatthe

sametimeisnotmorethan15.

3.7.3Forundergroundorsemi-undergroundfactorybuildings(includingbasementandsemi-

basement),theClassAfiredoorinafirewallofthefirecompartmentthatleadstotheadjoining

firecompartmentmaybeusedasthesecondexit,butatleastoneindependentexitdirectlyleading

totheoutdoorsmustbeprovidedforeachfirecompartment.

3.7.4Thedistancefromanypointtothenearestexitinthefactorybuildingsshallbenotgreaterthan

thosespecifiedinTable3.7.4.

·23·Table3.7.4Distancefromanypointtothenearestexitinthefactorybuildings(m)

Undergroundorsemi-undergroundfactory

Firehazard

Fire-resistanceSingle-storeyMulti-storeyHigh-rise

classification

building(includingbasementandsemi-

classfactorybuildingfactorybuildingfactorybuilding

ofproduction

basement)

AClassⅠandⅡ3025--

BClassⅠandⅡ755030-

ClassⅠandⅡ806030

C40

ClassⅢ6040-

ClassⅠandⅡNotlimitedNotlimited5045

DClassⅢ6050--

ClassⅣ50---

ClassⅠandⅡNotlimitedNotlimited7560

EClassⅢ10075--

ClassⅣ60---

3.7.5Thetotalclearwidthofexitstairway,passagewayanddoorinthefactorybuildingsshallbe

determinedbycalculationbasedontheminimumclearwidthforevacuationper100personsnotless

thanthosespecifiedinTable3.7.5.However,theminimumclearwidthofexitstairway,passageway

anddoorshouldnotbelessthan1.10m,1.40mand0.90m,respectively.Iftheoccupantloadsarenot

equaloneachfloor,thetotalclearwidthofexitstairwayshallbedeterminedbycalculationfloorby

floor.Thetotalclearwidthofstairwaysonanyfloorshallbedeterminedbycalculationaccordingto

maximumoccupantloadsofthisfloorandthefloorsabove.

Table3.7.5Minimumclearwidthforevacuationper100personsofexitstairway,

passagewayanddoorinthefactorybuildings

Numberofstoreysinfactorybuilding(storey)1-23≥4

Minimumclearwidthforevacuation(m/100persons)0.600.801.00

Thetotalclearwidthoftheexteriordooronthefirstfloorshallbedeterminedbycalculation

accordingtotheoccupantloadsonthisfloorandthefloorsabove.Theminimumclearwidthofthedoor

shallbenotlessthan1.20m.

3.7.6Forhigh-risefactorybuildingandClassA,BandCmulti-storeyfactorybuildings,theexit

stairwayshallbeenclosedstairwayoroutdoorstairway.Forfactorybuildingshigherthan32m

andtheoperatorsoneachfloorexceeding10,theexitstairwayshallbesmokeproofstaircaseor

outdoorstairway.

3.8Evacuationofstorages

3.8.1Exitsofstoragesshallbeseparatedfromeachother.Foreachfirecompartmentoreachfloorina

firecompartment,thedistancebetweentwoadjacentexitsshallbenotlessthan5m.

3.8.2Thenumberofexitsforeachstorageshallbenotlessthan2;1exitispermittedprovided

2

thatthefirstfloorareaofastorageisnotgreaterthan300m.Atleast2exitsshouldbeprovided

foreachfirecompartmentinstoragetoleadtoexitpassageway,stairwayortheoutdoors.1exitis

2

permittedprovidedthatthefloorareaofafirecompartmentisnotgreaterthan100m.Thedoor

·24·leadingtotheexitpassagewayorstairwayshallbeClassBfiredoor.

3.8.3Thenumberofexitsofundergroundorsemi-undergroundstorages(includingbasement

andsemi-basement)shallbenotlessthan2;oneexitispermittedprovidedthatthefloorareaisnot

2

greaterthan100m.

Forundergroundorsemi-undergroundstorages(includingbasementandsemi-basement),

theClassAfiredoorinafirewallofthefirecompartmentthatleadstotheadjoiningfire

compartmentmaybeusedasthesecondexit,butatleastoneindependentexitdirectlyleadingto

theoutdoorsmustbeprovidedforeachfirecompartment.

3.8.4Theevacuationarrangementofcoldstore,grainsiloandbankvaultshallcomplywiththe

requirementsofthecurrentnationalstandardsGB50072CodeforDesignofColdStoreandGB50322

CodeforDesignofGrainSteelSilosrespectively.

2

3.8.5Wheretheareaoftheworkingareaatthetopofthegrainsiloislessthan1000mandthe

numberofoperatorsisnotmorethan2,1exitispermitted.

3.8.6TheoutdoormetalstairwayinstorageandsilomeetingtherequirementsofArticle6.4.5ofthis

codemaybepermittedtobetheexitstairway,providedthatthefire-resistanceratingoftheoutdoor

stairwaylandingofthesiloshallbenotlessthan0.25h.

3.8.7Theexitstairwayofhigh-risestorageshallbeenclosedstairway.

3.8.8Verticalliftingfacilityshouldbeinstalledoutsideforstoragesotherthanmulti-storeyClassE

storageswithClassⅠorClassⅡfire-resistanceclass.Ifitmustbeinstalledinside,itshallbeplacedin

ashaftwiththefire-resistanceratingoftheshaftwallnotlessthan2.00h.Thedoortotheindooror

outdoorliftingfacilityleadingtothestorageshallbeClassBfiredoororfireshuttercomplyingwiththe

requirementsofArticle6.5.3.

·25·4ClassA,B,Cliquidandgastanks(tankfarm)and

stackyardforcombustibles

4.1Generalrequirements

4.1.1ClassA,BandCliquidtankfarm,LPGtankfarm,combustibleandcombustion-supportinggas

tankfarmandstackyardforcombustibles,shallbelocatedattheedgeoftheurban(zone)orinthe

relativelyindependentandsafezone,andshouldbelocatedinthedownwinddirectionwiththeannual

minimumfrequency.

ClassA,BandCliquidtanks(tankfarm)shouldbelocatedinplaceswithlowerterrain,otherwise

fireprotectionmeasuresshallbetaken.

LPGtank(tankfarm)shouldbelocatedinflatoropenplaceswhereLPGisnoteasily

accumulated.

4.1.2ClassAliquidinbarrelsorcylindersshallnotbestoredoutdoors.

4.1.3Noncombustiblesolidwallwiththeheightnotlessthan1.0mshallbeprovidedaroundthe

LPGtankgroupsortankfarms.

4.1.4ClassA,BandCliquidtankfarm,LPGtankfarm,combustibleandcombustion-supportinggas

tankfarmandstackyardforcombustiblesshallbearrangedawayfromtheloadingandunloadingarea,

accessoryproductionareaandofficearea.

4.1.5TheminimumdistancebetweenClassA,B,Cliquidtanks,LPGtanks,combustibleor

combustion-supportinggastanks,combustiblesstacksandoverheadpowerlinesshallcomplywiththe

requirementsofArticle10.2.1ofthiscode.

4.2FireseparationdistanceofClassA,B,Cliquidtanks(tankfarm)

4.2.1FireseparationdistancebetweenClassA,B,Cliquidtanks(tankfarm),stacksofClassB,C

liquidbarrelsandotherbuildingsshallbenotlessthanthosespecifiedinTable4.2.1.

Table4.2.1FireseparationdistancebetweenClassA,B,Cliquidtanks(tankfarm),stacksofClassB,

Cliquidbarrelsandotherbuildings(m)

Buildings

Outdoor

ClassⅠandⅡ

Totalvolumeofatank

transformerand

Classfarmorstacksofbarrels

Podium,

distribution

ClassⅢClassⅣ

High-rise

3

V(m)

other

substation

civilbuilding

building

1≤V<504012152030

ClassAandB

50≤V<2005015202535

liquidtanks(tank

200≤V<10006020253040

farms)

1000≤V<50007025304050

5≤V<2504012152024

ClassCliquidtank250≤V<10005015202528

(tankfarm)1000≤V<50006020253032

5000≤V<250007025304040

·26·Notes:1WhereClassA,B,Cliquidtanksarearrangedinthesametankfarm,thetotalvolumeofthetankfarmmaybeconverted

33

accordingtothefollowings:1mClassAandBliquidsisequivalentto5mClassCliquid.

2Thedistancebetweentheouteredgeofthefiredikeofthestoragetankandtheadjacentbuildingshallbenotlessthan10m.

3FireseparationdistancefromClassA,B,Cliquidfixedrooftankfarmorsemi-openstackyard,stacksofClassBandC

liquidbarrelstoClassAfactorybuildings(storages)andcivilbuildingsshallbeincreasedby25%%ofthosespecifiedin

thistable.However,thefireseparationdistancefromClassA,Bliquidfixedrooftankfarmsorsemi-openstackyard,

stacksofClassBandCliquidbarrelstoClassAfactorybuildings(storage),podium,singleormulti-storeycivil

buildingsshallbenotlessthan25m,andthedistancetotheopenflameorsparkingsiteshallbeincreasedby25%%ofthose

forClassⅣⅣbuildingspecifiedinthistable.

4Fireseparationdistancebetweenfloatingrooftankfarmortankfarmwithliquid''sflashpointover120℃andother

buildingsmaybereducedby25%%ofthosespecifiedinthistable.

5Incaseseveraltankfarmsarearrangedonthesamelot,thefireseparationdistancebetweentankfarmsshallbenotless

thanthegreatervalueofthefireseparationdistancespecifiedinthistablefortankfarmwithdifferentvolumesand

ClassⅣbuildings.

3

6FordirectlyburiedClassA,BandCliquidhorizontaltanks,wherethevolumeofasingletankisnotgreaterthan50m

3

andthetotalvolumeisnotgreaterthan200m,thefireseparationdistancebetweenthehorizontaltanksandthe

buildingsmaybereducedby50%%ofthosespecifiedinthistable.

7Outdoortransformeranddistributionsubstationarethosewiththevoltageof35kV-500kVandthecapacityofeach

transformernotlessthan10MV·A,oroutdoorstepdownsubstationsforindustrialusewiththetotaloilamountgreater

than5t.

4.2.2FireseparationdistancebetweenanytwoClassA,B,Cliquidtanksshallbenotlessthan

thosespecifiedinTable4.2.2.

Table4.2.2FireseparationdistancebetweenanytwoClassA,B,Cliquidtanks(m)

Fixedrooftank

Floatingrooftankorstorage

Horizontal

Classificationtankwithnitrogen-filling

Semi-

AbovegroundUndergroundtank

undergroundprotectionequipment

V≤10000.75D

ClassAand

0.5D0.4D0.4D

Volume

Bliquidtank

V>10000.6D

ofsingle

≥0.8m

tank

ClassC

3

V(m)Unlimited0.4DUnlimitedUnlimited--

liquidtank

Notes:1Disthediameter(m)ofthelargeradjacentverticalstoragetank.Thediameteroftherectangularstoragetankishalfof

thesumofthelong-sideandshort-sideoftherectangular.

2Fireseparationdistancebetweenanytwotankswithdifferentliquidsanddifferenttanktypesshallbenotlessthanthe

greatervaluespecifiedinthistable.

3Fireseparationdistancebetweenanytworowsofhorizontaltanksshallbenotlessthan3m.

3

4Wherethevolumeofsingletankisnotgreaterthan1000mandfixedcoolingsystemisprovided,thefireseparation

distancebetweenabovegroundfixedrooftanksofClassAandBliquidsshallbenotlessthan0.6D.

5Whereabovegroundstoragetankisprovidedwithsubsurfaceinjectionfoamextinguishingsystem,fixedcoolingwater

systemandfoamfireextinguishingfacilitiesusedforputtingoutliquidfireinthefiredike,thefireseparationdistance

betweenanytwostoragetanksmaybereduced,butshouldnotbelessthan0.4D.

6Forthecombustibleliquidwiththeflashpointgreaterthan120℃,wherethevolumeofasingletankisgreaterthan

3

1000m,thefireseparationdistancebetweenanytwostoragetanksshallbenotlessthan5m;wherethevolumeofa

3

singletankisnotgreaterthan1000m,thefireseparationdistanceshallbenotlessthan2m.

4.2.3WhereClassA,BandCliquidtanksarearrangedbygroup,thefollowingrequirements

shallbemet:

·27·1Thevolumeofasingletankandthetotalvolumeofthetankgroupshallbenotgreater

thanthosespecifiedinTable4.2.3.

3

Table4.2.3MaximumvolumeofClassA,BandCliquidtanksarrangedbygroup(m)

ClassMaximumvolumeofasingletankMaximumvolumeofatankgroup

1000

ClassAandBliquid200

ClassCliquid5003000

2Thestoragetanksinagroupshallnotbearrangedinmorethantworows.Thefire

separationdistancebetweenverticaltanksforClassAandBliquidsshallbenotlessthan2m,and

thatbetweenhorizontaltanksforClassAandBliquidsshallbenotlessthan0.8m.Thefire

separationdistancebetweenClassCliquidtanksisnotlimited.

3Fireseparationdistancebetweenstoragetankgroupsshallbedeterminedaccordingtothe

requirementsofArticle4.2.2ofthiscodebyfirstlyconvertingthestoragetanksinthegroupbased

onthetypeandtotalvolumeintostandardsingletankofthesameclass.

4.2.4Fortheabovegroundandsemi-undergroundtankfarmsofClassA,BandCliquids,thestorage

tankswiththesameorsimilarfirehazardshouldbearrangedwithinafiredike.Storagetankforboil-

overoilandthatfornon-oil-overoilshallnotbearrangedinthesamefiredike.Abovegroundandsemi-

undergroundstoragetanksshallnotbearrangedinthesamefiredikewiththeundergroundstoragetank.

4.2.5Noncombustiblefiredikeshallbearrangedaroundtheabovegroundandsemi-underground

storagetanksorstoragetankgroupforClassA,BandCliquids.Thearrangementoffiredikeshall

complywiththefollowingrequirements:

1Thestoragetanksinthesamefiredikeshouldnotbearrangedinmorethan2rows.The

3

volumeofasingletanknotgreaterthan1000mandtheliquidtankswiththeflashpointgreaterthan

120℃shouldnotbearrangedinmorethan4rows.

2Theeffectivecapacityofafiredikeshallbenotlessthanthevolumeofthemaximumstorage

tanktherein.Forfloatingrooftank,theeffectivecapacityofafiredikemaybehalfofthevolumeofthe

tankwithmaximumvolume.

3Thehorizontaldistancefromtheinneredgeofthefirediketotheouterwallofthevertical

tankshallbenotlessthanhalfoftheheightofthetankwall.Thehorizontaldistancefromthe

inneredgeofthefirediketothehorizontaltankshallbenotlessthan3m.

4Thedesignedheightofthefiredikeshallbe0.2mhigherthanthecalculatedheight,and

theheightshallbe1.0m--2.2m;thefootboardconvenientforthefire-fightingandrescuestaffgoing

inandoutofthefiredikeshallbeprovidedatreasonablelocation.

5Fortheabovegroundandsemi-undergroundstoragetanksusedforboil-overoil,every

storagetankshallbeprovidedwithafiredikeorfireseparationdike.

6Oilysewershallbeprovidedwithwatersealfacilitiesattheexitofthefiredike;rain

drainagepipesshallbeprovidedwithsealingandisolationdevicessuchasvalves.

4.2.6Forthesemi-openstackyardforClassAliquid,stackyardforbarreledClassBandCliquidsand

liquidtanks(tankfarm)withflashpointgreaterthan120℃,firedikesmaynotberequiredwhen

measurestopreventliquidfromflowinghavebeentaken.

4.2.7FireseparationdistancefromClassA,BandCliquidtankstothepumproomandliquidloading

andunloadingarmsshallbenotlessthanthosespecifiedinTable4.2.7.

·28·Table4.2.7FireseparationdistancefromClassA,BandCliquidtanksandthe

pumproomandliquidloadingandunloadingarms(m)

LiquidclassificationandstoragetanktypePumproomRailwayorautomobileloadingandunloadingarms

Domerooftank1520

ClassAandBliquidtank

Floatingrooftank1215

ClassCliquidtank1012

3

Notes:1ForClassAandBliquidtankswithtotalvolumenotgreaterthan1000mandClassCliquidtankwithtotalvolumenotgreater

3

than5000m,thefireseparationdistancemaybereducedby25%ofthosespecifiedinthistable.

2Thedistancefrompumproomandliquidloadingandunloadingarmstotheouteredgeofthefiredikeofthestoragetankshall

benotlessthan5m.

4.2.8FireseparationdistancefromtheloadingandunloadingarmsofClassA,BandCliquidstothe

buildingorthein-factoryrailwaytrackshallbenotlessthanthosespecifiedinTable4.2.8.

Table4.2.8FireseparationdistancefromtheloadingandunloadingarmsofClassA,

BandCliquidstobuildingorin-factoryrailwaytrack(m)

Building

In-factoryrailway

NamePumproom

track

ClassⅠandⅡClassⅢClassⅣ

Loadingandunloadingarmsof

14161820

ClassAandBliquid

8

Loadingandunloadingarmsof

10121410

ClassCliquid

Note:FireseparationdistancefromtheloadingandunloadingarmstoClassA,BandCliquidloadingandunloadingrailwayusedfor

directlyloadingandunloadingisnotlimited.

4.2.9FireseparationdistancebetweenClassA,BandCliquidtanksandrailway/roadshallbenot

lessthanthosespecifiedinTable4.2.9.

Table4.2.9FireseparationdistancebetweenClassA,BandCliquidtanksandrailway/road(m)

In-factoryroadside

Centerlineof

Centerlineofoff-factory

Name

Off-factoryroadside

railwayin-factoryrailway

MainSecondary

ClassAandBliquidtanks3525201510

ClassCliquidtank302015105

4.2.10Thedistancebetweensurgetankandtheloadingandunloadingrailwaylineshallbenotlessthan6m.

4.2.11Fireseparationdistancebetweenthetanks(tankfarm)oftheoildepotandthebuilding,the

arrangementoftanks,fireseparationdistancebetweenthestoragetanksintheoildepot,fireseparation

distancebetweenstoragetankandsuchbuildingsaspumproomandliquidloadingandunloadingarms

intheoildepotetc.,shallcomplywiththerequirementsofthecurrentnationalstandardGB50074Code

forDesignofOilDepot.

4.3Fireseparationdistanceofcombustibleandcombustion-

supportinggastanks(tankfarm)

4.3.1Fireseparationdistancebetweencombustiblegastankandthebuilding,storagetank,and

stackyardshallcomplywiththefollowingrequirements:

·29·1Fireseparationdistancebetweenwetcombustiblegastankandbuilding,storagetank,

stackyardshallbenotlessthanthosespecifiedinTable4.3.1.

Table4.3.1Fireseparationdistancebetweenwetcombustiblegastankandbuilding/storagetank/stackyard(m)

3

Wetcombustiblegastank(totalvolumeV,m)

Name

1000≤10000≤50000≤100000≤

V<1000

V<10000V<50000V<100000V<300000

ClassAstorageClassA,BandCliquidtanks

stackyardforcombustiblesoutdoortransformerand2025303540

distributionsubstationopenflameorsparkingsite

2530354045

High-risecivilbuildings

1820253035

Podium;single-,multi-storeycivilbuildings

ClassⅠandⅡ1215202530

Other

ClassⅢ1520253035

buildings

ClassⅣ2025303540

Note:Thetotalvolumeofcombustiblegastankwithconstantvolumeshallbecalculatedaccordingtotheproductofthegeometrical

35

volumeofthestoragetank(m)andthedesignedstoragepressure(absolutepressure,10Pa).

2Fireseparationdistancebetweenthecombustiblegastankwithconstantvolumeandthe

building,storagetankandstackyardshallbenotlessthanthosespecifiedinTable4.3.1.

3Fireseparationdistancebetweendrycombustiblegastankandbuilding,storagetank,and

stackyard:wherethedensityofthecombustiblegasisgreaterthanthatoftheair,thedistanceshall

beincreasedby25%%ofthosespecifiedinTable4.3.1;wherethedensityofcombustiblegasissmaller

thanthatoftheair,thedistanceshallbedeterminedaccordingtothosespecifiedinTable4.3.1.

4Fireseparationdistancefromsuchauxiliaryfacilitiesaswatersealedwell,oilpumproom

andelevatorroomofwetordrycombustiblegastanktothestoragetankmaybearranged

accordingtotheprocessrequirements.

5Fireseparationdistancebetweenthecombustiblegastankwithvolumenotgreaterthan

3

20mandthefactorybuildingusingthetankisnotlimited.

4.3.2Fireseparationdistancebetweenthecombustiblegastanks(tankfarms)shallcomplywith

thefollowingrequirements:

1Fireseparationdistancebetweenwetcombustiblegastanksorbetweendrycombustible

gastanksorbetweenwetcombustiblegastankanddrycombustiblegastankshallbenotlessthan

1/2ofthediameterofthelargeradjacenttank.

2Fireseparationdistancebetweencombustiblegastankswithconstantvolumeshallbenot

lessthan2/3ofthediameterofthelargeradjacenttank.

3Fireseparationdistancefromcombustiblegastankwithconstantvolumetothewetordry

combustiblegastankshallbenotlessthan1/2ofthediameterofthelargeradjacenttank.

4Wherethetotalvolumeofseveralcombustiblegastankswithconstantvolumeisgreater

3

than200000m,theyshallbearrangedbygroup.Fireseparationdistancebetweenhorizontaltank

groupsshallbenotlessthanhalfofthelengthofthelargeradjacenttank;fireseparationdistance

betweensphericaltankgroupsshallbenotlessthanthediameterofthelargeradjacenttank,and

shallbenotlessthan20m.

·30·4.3.3Fireseparationdistancebetweentheoxygentankandthebuilding,storagetankand

stackyardshallcomplywiththefollowingrequirements:

1Fireseparationdistancebetweenthewetoxygentankandthebuilding,storagetankand

stackyardshallbenotlessthanthosespecifiedinTable4.3.3.

Table4.3.3Fireseparationdistancebetweenthewetoxygentankandbuilding/storagetank/stackyard(m)

3

Wetoxygentank(totalvolumeV,m)

Name

V≤10001000<V≤50000V>50000

Openflameorsparkingsite253035

ClassA,B,Cliquidtanks,combustiblesstackyards,ClassA

202530

storage,outdoortransformeranddistributionsubstations

Civilbuildings182025

ClassⅠandⅡ101214

OtherbuildingsClassⅢ121416

ClassⅣ141618

Note:Thetotalvolumeofoxygentankwithconstantvolumeshallbecalculatedaccordingtotheproductofthegeometricalvolume

35

ofthestoragetank(m

)andthedesignedstoragepressure(absolutepressure,10Pa).

2Fireseparationdistancebetweentheoxygentanksshallbenotlessthan1/2ofthe

diameterofthelargeradjacenttank.

3Fireseparationdistancebetweentheoxygentankandthecombustiblegastankshallbe

notlessthanthediameterofthelargeradjacenttank.

4Fireseparationdistancefromtheoxygentankwithconstantvolumetothebuilding,tank

andstackyardshallbenotlessthanthosespecifiedinTable4.3.3.

5Fireseparationdistancebetweentheoxygentankandoxygenstationmaybedetermined

accordingtotherequirementsoftheprocesslayout.

3

6Fireseparationdistancebetweentheoxygentankwithvolumenotgreaterthan50mand

thefactorybuildingusingthetankisnotlimited.

33

Note:1mliquidoxygenisconvertedinto800mgaseousoxygenunderstandardcondition.

4.3.4Fireseparationdistancebetweentheliquidoxygentankandthebuilding,storagetankand

stackyardshallcomplywiththerequirementsforthefireseparationdistanceofwetoxygentankswith

thecorrespondingvolumeinArticle4.3.3ofthiscode.Thedistancebetweentheliquidoxygentankand

itspumproomshouldnotbelessthan3m.Thefireseparationdistancefromtheliquidoxygentankwith

3

totalvolumenotmorethan3mtothebuildingusingthetanksshallcomplywiththefollowing

requirements:

1WhenlocatedinthededicatedClassⅠorClassⅡbuildings,thefireseparationdistanceshall

benotlessthan10m.

2WhenlocatedinthededicatedClassⅠorClassⅡbuilding,andthesidefacingtothebuilding

isfirewallwithoutdoor,windoworotheropenings,thefireseparationdistanceisnotlimited.

3Whenmeasureshavebeentakentoprotectthelowtemperatureliquidoxygentank,thefire

separationdistanceshallbenotlessthan5m.

Theliquidoxygentankatthegassupplystationinthemedicalorganizationsshallcomplywiththe

followingrequirements:

·31·3

1Thevolumeofasingletankshallben

溫馨提示

  • 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請下載最新的WinRAR軟件解壓。
  • 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
  • 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁內(nèi)容里面會有圖紙預(yù)覽,若沒有圖紙預(yù)覽就沒有圖紙。
  • 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
  • 5. 人人文庫網(wǎng)僅提供信息存儲空間,僅對用戶上傳內(nèi)容的表現(xiàn)方式做保護處理,對用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對任何下載內(nèi)容負責(zé)。
  • 6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請與我們聯(lián)系,我們立即糾正。
  • 7. 本站不保證下載資源的準確性、安全性和完整性, 同時也不承擔(dān)用戶因使用這些下載資源對自己和他人造成任何形式的傷害或損失。

評論

0/150

提交評論